Error Code
Name
Description
225
Invalid DNP unsolicited
response mode
The unsolicited response mode code is not valid in the
configuration.
226
Invalid DNP unsolicited
response minimum quantity
for Class 1
The unsolicited response minimum quantity for Class
1 is not valid in the configuration. Value must be an
integer in the range of 1 to 255.
227
Invalid DNP unsolicited
response minimum quantity
for Class 2
The unsolicited response minimum quantity for Class
2 is not valid in the configuration. Value must be an
integer in the range of 1 to 255.
228
Invalid DNP unsolicited
response minimum quantity
for Class 3
The unsolicited response minimum quantity for Class
3 is not valid in the configuration. Value must be an
integer in the range of 1 to 255.
230
Invalid DNP unsolicited
response destination
address
The unsolicited response destination address is not
valid in the configuration. Value must be in the range
of 1 to 65534.
6.1.2 Command Error Codes
Command error codes are generated by the module's program. These errors are
generated when an error occurs when issuing a request or processing a
response of a command list function. The following tables list the command error
codes used in the module:
General Command Errors
Error Code
Name
Description
1
Device not defined
The IED slave address referenced in the command is
not defined in the module. Check to make sure there is
an entry in the slave table for each slave device
referenced in the command list.
2
Invalid command
This command is not valid. Check to make sure the
slave address parameter is greater than or equal to
zero and that the point count is not set to zero.
3
Object not supported
The data object in the command is not supported by
the module. Refer to the DNP subset for the Master
Port.
4
Command function not
supported
The function specified in the command is not
supported for the object type selected. Refer to the
DNP subset for the Master Port.
10
Invalid binary input poll
command
This binary input object command is not valid.
11
Invalid binary input event
poll command
This binary input event object poll command is not
valid.
20
Invalid binary output
command function
This binary output command function is not valid.
30
Invalid counter poll
command function
The counter object poll command contains an invalid
function code.
31
Invalid counter poll
command
This counter object poll command is not valid.
40
Invalid frozen counter poll
command
This frozen counter object poll command is not valid.
50
Invalid analog input poll
command
This analog input poll command is not valid.
51
Invalid analog input event
poll command
This analog input event poll command is not valid.