beautypg.com

Command error codes, General command errors, 2 command error codes – ProSoft Technology 5201-DFNT-DNPM User Manual

Page 35

background image

Reference DNPM

♦ ProLinx Gateway

Driver Manual

DNP 3.0 Master


ProSoft Technology, Inc.

Page 35 of 56

September 30, 2009

Error Code

Name

Description

225

Invalid DNP unsolicited
response mode

The unsolicited response mode code is not valid in the
configuration.

226

Invalid DNP unsolicited
response minimum quantity
for Class 1

The unsolicited response minimum quantity for Class
1 is not valid in the configuration. Value must be an
integer in the range of 1 to 255.

227

Invalid DNP unsolicited
response minimum quantity
for Class 2

The unsolicited response minimum quantity for Class
2 is not valid in the configuration. Value must be an
integer in the range of 1 to 255.

228

Invalid DNP unsolicited
response minimum quantity
for Class 3

The unsolicited response minimum quantity for Class
3 is not valid in the configuration. Value must be an
integer in the range of 1 to 255.

230

Invalid DNP unsolicited
response destination
address

The unsolicited response destination address is not
valid in the configuration. Value must be in the range
of 1 to 65534.

6.1.2 Command Error Codes

Command error codes are generated by the module's program. These errors are
generated when an error occurs when issuing a request or processing a
response of a command list function. The following tables list the command error
codes used in the module:

General Command Errors

Error Code

Name

Description

1

Device not defined

The IED slave address referenced in the command is
not defined in the module. Check to make sure there is
an entry in the slave table for each slave device
referenced in the command list.

2

Invalid command

This command is not valid. Check to make sure the
slave address parameter is greater than or equal to
zero and that the point count is not set to zero.

3

Object not supported

The data object in the command is not supported by
the module. Refer to the DNP subset for the Master
Port.

4

Command function not
supported

The function specified in the command is not
supported for the object type selected. Refer to the
DNP subset for the Master Port.

10

Invalid binary input poll
command

This binary input object command is not valid.

11

Invalid binary input event
poll command

This binary input event object poll command is not
valid.

20

Invalid binary output
command function

This binary output command function is not valid.

30

Invalid counter poll
command function

The counter object poll command contains an invalid
function code.

31

Invalid counter poll
command

This counter object poll command is not valid.

40

Invalid frozen counter poll
command

This frozen counter object poll command is not valid.

50

Invalid analog input poll
command

This analog input poll command is not valid.

51

Invalid analog input event
poll command

This analog input event poll command is not valid.

This manual is related to the following products: