OBJECT REQUEST

RESPONSE

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

NOTES

6 16-Bit

Binary

Counter Without
Flag

1, 7, 8,
9, 10

06 129,

130

00, 01

16

Master will generate and process this
variation

7 32-Bit

Delta

Counter Without
Flag

129,
130

00, 01

32

Master will process this variation

8 16-Bit

Delta

Counter Without
Flag

129,
130

00, 01

16

Master will process this variation

21 0

Frozen Counter: All
Variations

1 06

32

Master will generate this variation

1 32-Bit

Frozen

Counter

129,
130

00, 01

40

Master will process this variation.
Status flags are discarded.

2 16-Bit

Frozen

Counter

129,
130

00, 01

24

Master will process this variation.
Status flags are discarded.

3

32-Bit Frozen Delta
Counter

40

4

16-Bit Frozen Delta
Counter

24

5

32-Bit Frozen
Counter With Time
Of Freeze

88

6

16-Bit Frozen
Counter With Time
Of Freeze

72

7

32-Bit Frozen Delta
Counter With Time
Of Freeze

88

8

16-Bit Frozen Delta
Counter With Time
Of Freeze

72

9

32-Bit Frozen
Counter Without
Flag

1

06 129,

130

00, 01

32

Master will generate and process this
variation

10 16-Bit

Frozen

Counter Without
Flag

1

06 129,

130

00, 01

16

Master will generate and process this
variation

11 32-Bit Frozen Delta

Counter Without
Flag

32

12 16-Bit Frozen Delta

Counter Without
Flag

16

22 0 Counter

Change

Event: All
Variations

1

06, 07, 08

Master will not generate a request for
this variation

This manual is related to the following products: