ProSoft Technology 5201-DFNT-DNPM User Manual
Page 40
DNPM ♦ ProLinx Gateway
Reference
DNP 3.0 Master
Driver Manual
Page 40 of 56
ProSoft Technology, Inc.
September 30, 2009
OBJECT REQUEST
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
6 16-Bit
Binary
Counter Without
Flag
1, 7, 8,
9, 10
06 129,
130
00, 01
16
Master will generate and process this
variation
7 32-Bit
Delta
Counter Without
Flag
129,
130
00, 01
32
Master will process this variation
8 16-Bit
Delta
Counter Without
Flag
129,
130
00, 01
16
Master will process this variation
21 0
Frozen Counter: All
Variations
1 06
32
Master will generate this variation
1 32-Bit
Frozen
Counter
129,
130
00, 01
40
Master will process this variation.
Status flags are discarded.
2 16-Bit
Frozen
Counter
129,
130
00, 01
24
Master will process this variation.
Status flags are discarded.
3
32-Bit Frozen Delta
Counter
40
4
16-Bit Frozen Delta
Counter
24
5
32-Bit Frozen
Counter With Time
Of Freeze
88
6
16-Bit Frozen
Counter With Time
Of Freeze
72
7
32-Bit Frozen Delta
Counter With Time
Of Freeze
88
8
16-Bit Frozen Delta
Counter With Time
Of Freeze
72
9
32-Bit Frozen
Counter Without
Flag
1
06 129,
130
00, 01
32
Master will generate and process this
variation
10 16-Bit
Frozen
Counter Without
Flag
1
06 129,
130
00, 01
16
Master will generate and process this
variation
11 32-Bit Frozen Delta
Counter Without
Flag
32
12 16-Bit Frozen Delta
Counter Without
Flag
16
22 0 Counter
Change
Event: All
Variations
1
06, 07, 08
Master will not generate a request for
this variation