DNPM Protocol Configuration

DNPM ♦ ProLinx Gateway

Driver Manual

DNP 3.0 Master


ProSoft Technology, Inc.

Page 19 of 56

September 30, 2009

Note: CROB commands (object 12) exceeding a count of 16 are not recommended. Many IEDs
only support one transport layer and a count > 16 may cause the IED device to not accept the new
data value being written by the ProLinx module.

The following table aids in defining the command list as it displays the values
required for certain DNP data types:

Digital input

Digital input Events Digital Output

Counter

0 Port/Flags

Port/Flags

Port/Flags

Port/Flags

1

Slave Address

Slave Address

Slave Address

Slave Address

2 1

2

12

20

3 0, 1 or 2

0, 1, 2 or 3

1*

0, 5 or 6

4

1*

1*

3, [4], 5 or 6

1, 7, 8, 9 or 10

5 Address in Slave

Address in Slave

Address in Slave

Address in Slave

6

# of Points

# of Points

# of Points

# of Points

7 IED DB Address

IED DB Address

IED DB Address

8

Poll Interval

Poll Interval

Poll Interval

Poll Interval

Frozen Counter

Analog Input

Analog Input Events Analog Output

0 Port/Flags

Port/Flags

Port/Flags

Port/Flags

1

Slave Address

Slave Address

Slave Address

Slave Address

2 21

30

32

41

3

0, 9 or 10

0, 1, 2, 3 or 4

0, 1, 2, 3 or 4

2*

4 1*

1*

1*

3, [4], 5 or 6

5

Address in Slave

Address in Slave

Address in Slave

Address in Slave

6 # of Points

# of Points

# of Points

# of Points

7

IED DB Address

IED DB Address

IED DB Address

8 Poll Interval

Poll Interval

Poll Interval

Poll Interval

Time and Date

Class 0

Class 1

Class 2

0 Port/Flags

Port/Flags

Port/Flags

Port/Flags

1

Slave Address

Slave Address

Slave Address

Slave Address

2 50

60

60

60

3

1*

1

2

3

4 2*

5

6 1

1

1

1

7

8

Poll Interval

Poll Interval

Poll Interval

Poll Interval