Operation Messages
After the initialization step, the following message pattern will be repeated.
Code Message
OK: Module is communicating with processor
ERR: Module is unable to communicate with processor. For
this scenario, the
with "Processor faulted or is in program mode".
Module IP address
OK: Port is communicating without error
Communication Errors: port is having communication errors.
Refer to PCB diagnostics for further information about the
error.
The LEDs indicate the module's operating status as follows:
Module Color
Status
Indication
On
The MVI56E-MNETR is working normally.
APP Amber
Off
The MVI56E-MNETR module program has recognized a
communication error on its Application Port(s).
Off
The card is not receiving adequate power, or is not securely
plugged into the rack.
Green
The module is operating normally.
OK
Red/
Green
Red
The module has detected an internal error, or is being
initialized. If the LED remains red for over 10 seconds, the
module is not working. Remove it from the rack and re-insert it
to restart its internal program.
Off
The battery voltage is OK and functioning.
BAT Red
On
The battery voltage is low, or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If BAT LED still does not go off, contact ProSoft
Technology, as this is not a user-serviceable item.
4.9.1 Configuration
Error
Word
If a configuration error is found for the Client, the Client configuration error word
will have a value other than zero. The configuration error word bits have the
following definitions:
Bit Description
Value
0
0x0001
1
0x0002
2
0x0004
3
0x0008
4
Invalid retry count parameter
0x0010
5
The float flag parameter is not valid.
0x0020
6
The float start parameter is not valid.
0x0040
7
The float offset parameter is not valid.
0x0080