Backplane data transfer – ProSoft Technology MVI56E-MNETR User Manual
Page 104

MVI56E-MNETR ♦ ControlLogix Platform
Reference
Modbus TCP/IP Interface Module with Reduced Data Block
User Manual
Page 104 of 153
ProSoft Technology, Inc.
August 31, 2009
5.2.3 Backplane Data Transfer
The MVI56E-MNETR module communicates directly over the ControlLogix
backplane. Data is paged between the module and the ControlLogix processor
across the backplane using the module's input and output images. The update
frequency of the images is determined by the scheduled scan rate defined by the
user for the module and the communication load on the module. Typical updates
are in the range of 1 to 10 milliseconds.
This bi-directional transference of data is accomplished by the module filling in
data in the module's input image to send to the processor. Data in the input
image is placed in the Controller Tags in the processor by the ladder logic. The
input image for the module is set to 42 words. This data is transferred in the
scheduled I/O timeslot.
The processor inserts data to the module's output image to transfer to the
module. The module's program extracts the data and places it in the module's
internal database. The output image for the module is set to 42 words. This data
is transferred in the scheduled I/O timeslot.
The following illustration shows the data transfer method used to move data
between the ControlLogix processor, the MVI56E-MNETR module and the
Modbus TCP/IP Network.