MVI56E-MNETR ♦ ControlLogix Platform
Start Here
Modbus TCP/IP Interface Module with Reduced Data Block
User Manual
Page 32 of 153
ProSoft Technology, Inc.
August 31, 2009
This action opens the S
ELECT
M
ODULE
dialog box.
2 Select the 1756-M
ODULE
(G
ENERIC
1756
M
ODULE
)
from the list and click OK.
This action opens the N
EW
M
ODULE
dialog box.
3 Set the Module Properties values as follows:
Parameter Value
Name
Enter a module identification string. The recommended value is
MNETR.
Description
Enter a description for the module. Example: Modbus TCP/IP
Interface Module with Reduced Data Block.
Comm Format
Select D
ATA
-INT
(Very Important)
Slot
Enter the slot number in the rack where the MVI56E-MNETR
module is to be installed.
Input Assembly Instance
1
Input Size
42
Output Assembly Instance
2