3 Set the Module Properties values as follows:
Parameter Value
Name
Enter a module identification string. The recommended value is
MNETR.
Description
Enter a description for the module. Example: Modbus TCP/IP
Interface Module with Reduced Data Block.
Comm Format
Select D
ATA
-INT
(Very Important)
Slot
Enter the slot number in the rack where the MVI56E-MNETR
module is or will be located.
Input Assembly Instance
1
Input Size
42
Output Assembly Instance
2
Output Size
42
Configuration Assembly Instance 4
Configuration Size
0
4 On the C
ONNECTION
tab, set the RPI
value for your project. Fifty (50)
milliseconds is usually a good starting value.