Normal Data Transfer
Normal data transfer includes the paging of the user data found in the module’s
internal database in registers 0 to 4999 and the status data. These data are
transferred through read (input image) and write (output image) blocks.
The following topics describe the function and structure of each block.
Status Read Data Block
This block is automatically copied from the module and contains status
information about the module.
Offset Description
Length
0
Write Block ID
1
1
Program Scan Counter
1
2 to 7
Block Transfer Status
6
8 to 9
Reserved Server Status
2
10 to 11
MNET Server Status
2
12 to 13
MBAP Server Status
2
14 to 23
MNET Client Status
10
24 to 40
Reserved
17
41
Read Block ID (-1 or 0)
1
MVI56E-MNETR Client Status
Offset Client
Status
3
Total number of command list requests
4
Total number of command list responses
5
Total number of command list errors
6
Total number of requests of slave
7
Total number of responses
8
Total number of errors sent
9
Total number of errors received
10
Total number of Configuration Errors
11
Total number of Current Errors
12 Last
Error
Read Block
These blocks of data transfer information from the module to the ControlLogix
processor. The following table describes the structure of the input image.
Offset Description
Length
0
Write Block ID
1
1 to 40
Read Data
40
41
Read Block ID
1