4 operation status register set, 5 questionable status register set, Operation status register set -7 – KEPCO KLP Series Developer's Guide, Rev 1 User Manual
Page 17: Questionable status register set -7

KLP-DEV 031113
1-7
1.2.7.4
OPERATION STATUS REGISTER SET
The Operation Status register set is comprised of condition, transition, event and enable regis-
ters (see Figure 1-2). Appendix B, PAR’s B.58 through B.61 provide detailed explanations of the
queries/commands for reading and modifying these registers as applicable; the transition regis-
ter cannot be modified.
The Operation condition registers record conditions which are a part of the instrument’s normal
operation. The definition of each of these bits (condition register) is as follows:
• 0 through 4 — Not used (always zero).
• 5 - Waiting for Trigger Summary — 1 indicates the unit is waiting for trigger
• 6 and 7 — Not used (always zero).
• 8 - Constant Voltage — 1 indicates the instrument is in constant voltage mode.
• 9 — Not used (always zero).
• 10 - Constant Current — 1 indicates the instrument is in constant current mode.
• 11 through 13 — Not used (always zero).
• 14 - Program Running — 1 indicates the program is running.
• 15 — Not used (always zero).
1.2.7.5
QUESTIONABLE STATUS REGISTER SET
The Questionable Status register set is comprised of conditon, transition, event and enable reg-
isters (see Figure 1-2). Appendix B, PAR’s B.63 through B.66 provide detailed explanations of
the queries/commands for reading and modifying these registers as applicable; the transition
register cannot be modified.
The Questionable Condition register (see Figure 1-2) contains status bits representing data/sig-
nals which give an indication of the quality of various aspects of the signal.
A bit set in the Questionable Condition register indicates that the data currently being acquired
or generated is of questionable quality due to some condition affecting the parameter associ-
ated with that bit.
• 0 - Overvoltage Error — 1 indicates an overvoltage fault has been detected.
• 1 - Overcurrent Error — 1 indicates an overcurrent fault has been detected.
• 2 - Power Lead Error — 1 indicates that output lead connections are not complete.
• 3 - Overtemperature Error — 1 indicates a thermal error has been detected.
• 4 - Input Power Error — 1 indicates input mains error.
• 5 - Fan Error — 1 indicates inoperative fan.
• 6 - Master/Slave Error — 1 indicates communication error between master and slave
units.
• 7 - 15 — Not used (always zero).