Precision Digital PD6800 User Manual
Page 25

PD6800-0L1 Loop-Powered Process Meter
Instruction Manual
25
Minimum Input Span
The minimum input span is the minimum difference between input 1 and input 2 
signals required to complete the calibration or scaling of the meter. The minimum 
span is 0.10 mA. 
Scale Error Message (SPN ERR)
If the minimum span is not maintained, the meter will show a span error (SPN ERR) 
and revert to input 2, allowing the appropriate input signals to be applied. 
 
Scaling the Tank Level Indicator (PERCENT)
The display includes a 20-segment tank level indicator. This menu sets full and 
empty values, in engineering units, for the tank level indicator. 
This value may differ from the 20 mA full-scale and 4 mA empty-scale values 
programmed in the Scale menu. This is ideal for level transmitters that output less 
than 20 mA at the maximum height of the tank or pit or more than 4 mA at the 
minimum height. 
As an example, when using a level transmitter that outputs 20 mA at 25 meters, the 
tank height indicator may be set for a maximum of 10 meters. When the meter 
reaches 10 meters on the display, the tank height indicator will show full, even though 
the input is not 20 mA. 
 
set
up
-010.0
0300.0
