Exported event data, Exported sensor data, Exported event data exported sensor data – Enviro EA800 User Manual
Page 73

Maintenance
D-011-0152
69
Exported Event Data
The following is an example of exported event data:
12/24/2007 07:06:03 PM,Sensor deleted,1
12/24/2007 07:10:50 PM,Sensor added,1
12/25/2007 02:27:14 PM,System power on,1
12/25/2007 02:27:50 PM,Sensor deleted,1
12/25/2007 02:36:02 PM,Sensor added,1
12/25/2007 03:08:55 PM,Sensor deleted,1
12/25/2007 03:11:19 PM,Sensor added,1
The data presented provides the following event information:
Exported Sensor Data
The following is an example of exported sensor data. The data is collected from all sensors at the intervals as
specified in the
Data Collection system setting (every 5 minutes in this example). Each sensor is allocated 11 data
fields and 11 data fields are provided for all 8 sensors, regardless of how many sensors are actually connected.
12/26/2007 09:55:00
PM,17,C,,0,0,0,0,0,0,0,0,69,F,,0,0,0,0,0,0,0,0,69,F,,0,0,0,0,0,0,0,0,1,,,0,0,0,0,0,0,0,0,66,F,255,0,0
,0,0,0,0,0,0,65,F,105,0,0,0,0,0,0,0,0,,,,0,1,0,0,0,0,0,0,,,,0,1,0,0,0,0,0,0
12/26/2007 10:00:01
PM,17,C,,0,0,0,0,0,0,0,0,69,F,,0,0,0,0,0,0,0,0,69,F,,0,0,0,0,0,0,0,0,1,,,0,0,0,0,0,0,0,0,66,F,255,0,0
,0,0,0,0,0,0,65,F,90,0,0,0,0,0,0,0,0,,,,0,1,0,0,0,0,0,0,,,,0,1,0,0,0,0,0,0
12/26/2007 10:05:00
PM,17,C,,0,0,0,0,0,0,0,0,69,F,,0,0,0,0,0,0,0,0,69,F,,0,0,0,0,0,0,0,0,1,,,0,0,0,0,0,0,0,0,66,F,255,0,0
,0,0,0,0,0,0,65,F,75,0,0,0,0,0,0,0,0,,,,0,1,0,0,0,0,0,0,,,,0,1,0,0,0,0,0,0
12/26/2007 10:10:00
PM,17,C,,0,0,0,0,0,0,0,0,69,F,,0,0,0,0,0,0,0,0,69,F,,0,0,0,0,0,0,0,0,1,,,0,0,0,0,0,0,0,0,66,F,240,0,0
,0,0,0,0,0,0,65,F,75,0,0,0,0,0,0,0,0,,,,0,1,0,0,0,0,0,0,,,,0,1,0,0,0,0,0,0
12/26/2007 10:15:00
PM,17,C,,0,0,0,0,0,0,0,0,69,F,,0,0,0,0,0,0,0,0,69,F,,0,0,0,0,0,0,0,0,1,,,0,0,0,0,0,0,0,0,66,F,255,0,0
,0,0,0,0,0,0,65,F,65,0,0,0,0,0,0,0,0,,,,0,1,0,0,0,0,0,0,,,,0,1,0,0,0,0,0,0
12/26/2007 10:20:01
PM,17,C,,0,0,0,0,0,0,0,0,69,F,,0,0,0,0,0,0,0,0,69,F,,0,0,0,0,0,0,0,0,1,,,0,0,0,0,0,0,0,0,66,F,255,0,0
,0,0,0,0,0,0,65,F,75,0,0,0,0,0,0,0,0,,,,0,1,0,0,0,0,0,0,,,,0,1,0,0,0,0,0,0
Each entry is interpreted as:
12/26/2007 09:55:00 PM,(11 CSVs for Sensor 1),(11 CSVs for Sensor 2),(11 CSVs for Sensor 3),(11 CSVs for
Sensor 4),(11 CSVs for Sensor 5),(11 CSVs for Sensor 6),(11 CSVs for Sensor 7),(11 CSVs for Sensor 8)
There is a line feed and a carriage return character at the end of each The data collected at 09:55:00 in the data
log example above provides the sensor information shown below for Sensor 1. The data represented by each of
the 11 data fields is defined below and is applicable to each of the 8 sensors that may be connected.
■
Blank (,,): The data is null and is not valid for that sensor. For example, the LQI (signal strength) position is null
for wired sensors but shows the LQI value as shown for the two wireless sensors (255 and 105 respectively).
Where wireless sensors are not installed the LQI is also blank indicating that no reading is made.
■
0 (,0,): The data is valid and is valid data for that sensor’s data point.
Date and time of event
Event description
Code (For Factory Use)
12/24/2007 07:06:03 PM
Sensor deleted
1
Date and time of
reading
Sensor # 1
CSV1
Reading
CSV2
Unit of
Measure
CSV3
LQI
CSV4
Pause
CSV5
Pending
Alarms
CSV6
Low
CSV7
High
CSV8
Comm
CSV9
Fail
CSV10
No Data
CSV11
Low
Battery
12/26/2007
09:55:00 PM
17
C
Null
0
0
0
0
0
0
0
0