Appendix C - Battery Information

C1 Battery Bank Sizing

The size of the battery bank determines how long the inverter can
power the AC loads without recharging. The larger the battery bank,
the longer the run time. Size your battery bank to the system’s AC
load requirements and the length of time required to run the load
from the batteries. In general, the battery bank should not be dis-
charged more than 50%.

C2 Battery Types

Batteries are available in different sizes, amp-hour ratings, voltage,
and chemistries; they also come in liquid or gel, vented or non-
vented, etc. They are also available for starting applications (such
as an automobile starting battery) and deep discharge applications.
Only the deep cycle types are recommended for inverter applications.
Choose the batteries best suited for the inverter installation and cost.
Use only the same battery type for all batteries in the bank. For best
performance, all batteries should be from the same lot and date.
This information is usually printed on a label located on the battery.

C3 Battery Confi guration

The battery bank must be wired to match the inverter’s DC input
voltage specifi cations. In addition, the batteries can be wired to
provide additional run- time. The various wiring confi gurations are:

C3.1 Series Wiring

Wiring batteries in a series increases the total battery bank output
voltage. A series connection combines each battery in a string until
the voltage matches the inverter’s DC requirement. Even though there
are multiple batteries, the capacity remains the same. In the example
below (Figure C3-1), two 6 VDC/200 AHr batteries are combined into
a single string – resulting in a 12 VDC/200 AHr bank.

6 volts

(200 AHrs)

6 volts

(200 AHrs)

overcurrent protection

12 volt battery bank (total capacity = 200 AHrs)

To

12 VDC

Inverter

Figure C3-1, Series Battery Wiring

Appendix C - Battery Information