Magnum Energy MMS-E Series User Manual
Page 39

© 2011 Magnum Energy, Inc.
Table 3-2, Inverter/Charger Default Settings
03 Battery AmpHrs: This setting allows you to input the battery bank
size in amp-hours. This provides information to the charger on how
long to charge the batteries in the Absorb Charging stage.
04 Battery Type: This setting identifi es the type of batteries being used
in the system. This provides information to the charger to determine
what voltage level to use to charge the batteries.
05 Charge Rate: This setting can be used to turn off the charger, or
limit the amount of current that the charger can use (leaving more
current available to power loads); or, to ensure small battery banks
are not overheated because of a charge rate that is too high.
06 VAC Dropout: Sets the minimum AC voltage that must be pres-
ent on the AC input before the unit transfers from Standby Mode to
Inverter Mode. This protects the AC loads from utility outages and
brown-outs.
The ME-RC50 remote also provides the following features:
•
allows you to enable an equalize charge for certain battery
types
•
displays the inverter/charger’s operating status
•
provides fault information for troubleshooting
32
3.0 Operation
Function
Search Watts
5 Watts
10.0 VDC
LowBatCutOut
Battery AmpHrs
100%
Battery Type
Flooded – Liquid Lead Acid
Bulk = 14.6 VDC, Float = 13.4 VDC
Charge Rate
400 AmpHrs
(Absorb Time = 90 mins)
Default Settings
VAC Dropout
150 VAC