beautypg.com

6 grounding inverters – Magnum Energy ME-G Series User Manual

Page 34

background image

Page 25

©

2015 Sensata Technologies

Installation

2.6 Grounding

Inverters

The inverter/charger should always be connected to a permanent, grounded wiring system. An

inverter system that is properly grounded will limit the risk of electrical shock, reduce radio

frequency noise from the inverter, and minimize excessive surge voltages induced by lightning.

This is done by ensuring there is a well-defi ned, very low-resistance path from the electrical

system to the grounding system. This low-resistance path helps stabilize the electrical system

voltage with respect to ground and carries fault currents directly to ground if the electrical system

malfunctions.
The ME-G Series inverter/charger uses both AC and DC power. However, the AC electrical system

is isolated from the DC electrical system by an internal transformer. Although this inverter/charger

has two electrical systems, each electrical system must be properly grounded and connected to

a common point.
For proper grounding, each electrical system must connect all exposed metal parts of equipment

and one of the current carrying conductors together at a common point. This common point of

each electrical system is then connected to the common ground reference. This connection to the

common ground reference should only be made at one point in each electrical system; otherwise,

parallel paths will exist for the currents to fl ow. These parallel current paths would represent a

safety hazard and are not allowed in installations wired per the NEC/CEC.

2.6.1 Equipment

Grounding

The inverter case and all other non-current carrying exposed metal surfaces in the entire electrical

system that may be accidentally energized must be grounded. The equipment-grounding

conductor must be sized to safely carry the maximum ground-fault current likely to be imposed

on it from where a ground-fault may occur. In accordance with the NEC, use Table 2-4 to size the

equipment-grounding conductors. This table requires that the equipment-grounding conductor be

sized according to the rating of the overcurrent device protecting the circuit.

CAUTION: The connections and wiring for the equipment-grounding conductor must

be continuous to allow fault currents to properly operate overcurrent devices. Where

equipment is removed and this disconnects the bonding connection between the

grounding electrode conductor and exposed conducting surfaces, a bonding jumper

must be installed while the equipment is removed.

AC Side – Where the AC output from the inverter is connected to an AC load center, there should

be an equipment grounding conductor connected between the inverter case and the grounding

point in the AC load center. The AC equipment grounding conductor is sized per Table 2-4, and is

connected to the inverter’s AC equipment grounding terminal as shown in Figure 2-8.
DC Side – Since the currents on the DC side are higher than the AC side (10 times at 12 volts),

the equipment grounding needs are different. The DC equipment grounding conductor is sized

per Table 2-4, and connected to the DC equipment grounding terminal on the inverter as shown

in Figure 2-15.

Table 2-4, Equipment Grounding Conductor Sizing

Rating of Overcurrent

Device

Minimum Size of

Copper Ground Wire

15 amp

#14 AWG (2.1 mm

2

)

20 amp

#12 AWG (3.3 mm

2

)

30-60 amp

#10 AWG (5.3 mm

2

)

100 amp

#8 AWG (8.4 mm

2

)

200 amp

#6 AWG (13.3 mm

2

)

300 amp

#4 AWG (21.1 mm

2

)

400 amp

#3 AWG (26.6 mm

2

)