beautypg.com

Front view side view – Magnum Energy ME-G Series User Manual

Page 24

background image

Page 15

©

2015 Sensata Technologies

Installation

2.4.4

Wiring the Battery Bank

WARNING: Lethal currents will be present if the positive and negative cables attached

to the battery bank touch each other. During the installation and wiring process, ensure

the cable ends are insulated or covered to prevent touching/shorting the cables.
Info: DO NOT connect the DC wires from the battery bank to the inverter until: 1) all

DC and AC wiring are completed, 2) the correct DC and AC overcurrent protection has

been installed, and 3) the correct DC voltage and polarity have been verifi ed.
Info: For the ME-G Series inverter/charger to perform optimally, a minimum battery

bank of 200 AH is recommended for moderate loads (<1000W) and greater than 400

AH for heavy loads (≥1000W).

Depending upon the voltage of the batteries you use in the installation (6 or 12 VDC), the

batteries must be wired in series, parallel, or series-parallel to provide the correct voltage (see

Appendix B – Battery Information for guidance on wiring batteries together). The interconnecting

DC wires must be sized and rated exactly the same as those that are used between the battery

bank and the inverter.
Place the batteries as close as practical to the inverter, preferably in an insulated and ventilated

enclosure. Allow adequate space above the batteries to access the terminals and vent caps (as

applicable). Also, allow at least 1” (2.5 cm) of space between the batteries to provide good air

fl ow. DO NOT mount the batteries directly under the inverter.

CAUTION: Install batteries in a well ventilated area. Batteries can produce explosive

gases. For compartment/enclosure installations, always vent batteries to the outside.

Info: To ensure the best performance from your inverter system, batteries should be of

the same size, type, rating, and age. Do not use old or untested batteries.

2.4.5

Battery Temperature Sensor Installation and Wiring

The Battery Temperature Sensor (Figure 2-7) provides the inverter with precise battery temperature

information to automatically adjust the ABSORB and FLOAT charge voltage set points. This allows

the batteries to be correctly charged under extreme temperature changes.
If the temperature sensor is NOT installed and the batteries are subjected to large temperature

changes, battery life may be shortened.
The BTS cable may be extended—using a RJ11 connector (female to female) and a standard

phone cable with RJ11 connectors—to a maximum length of 40 feet (12 m). However, your

inverter to battery cable length shouldn’t exceed the recommended distance shown in Table 2-2.
To install the BTS:
1. Attach the ring terminal end of the Battery Temperature Sensor to the negative battery terminal;

see Figure 2-5 for proper connection to the battery terminal.

2. Route the sensor’s cable to the inverter following existing wire runs.
3. Connect the RJ11 connector end of the BTS cable to the yellow-labeled BTS Port on the

inverter (see Figure 1-1, Item 6).

Figure 2-7, Battery Temperature Sensor

FRONT VIEW

SIDE VIEW

~2"

~1"

~½”

0.375" diameter

Cable

~¾”

(~2.54 cm)

(~5.1 cm)

(~1.9 cm)

(~1.3 cm)

(~.95 cm)