Installation – Magnum Energy ME-G Series User Manual

Page 23

background image

©

2015 Sensata Technologies

Page 14

Installation

Table 2-2, DC Wire Size For Increased Distance (in free air)

Minimum Recommended DC Wire Size (one way)*

5 feet or less

(≤1.5 m)

5 to 10 feet

(1.5 to 3.1 m)

10 to 15 feet

(3.1 to 4.6m)

ME2012-G

#2/0 AWG

(67.4 mm

2

)

#4/0 AWG

(107.16 mm

2

)

#4/0 AWG

(107.16 mm

2

) x2

ME2512-G

#4/0 AWG

(107.16 mm

2

)

#4/0 AWG x2

(107.16 mm

2

) x2

not recommended

ME3112-G

#4/0 AWG

(107.16 mm

2

)

#4/0 AWG x2

(107.16 mm

2

) x2

not recommended

* Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F)

2.4.3

DC Cable Connections

Do not put anything between the DC cable ring lug and the battery terminal post or the fl at metal

part of the inverter’s DC terminal. When connecting the DC cable to the battery or inverter DC

terminals, the cable should be placed directly against the inverter or battery terminals. Incorrectly

installed hardware causes a high resistance connection, which could lead to poor inverter/charger

performance and may melt the cable and terminal connections.
Refer to Figures 2-5 and 2-6 to connect the DC cables and stack the hardware correctly. Tighten

the terminal connections from 10 to 12 lbf-ft (13.6 to 16.3 N-m).

CAUTION: The DC terminal and Flange/Kep nuts are made of stainless steel, which has

a high likelihood of seizure. To help prevent the bolt and nut from seizing—causing the

bolts to strip or snap/break-off—the use of anti-seize lubricant is highly recommended.

Info: If antioxidant grease or spray is used, apply it after all the connections have been

made and are properly tightened.

Info: A 1/2-inch wrench or socket is used to tighten the 5/16 SAE Flange/Kep nuts.

battery cable

(with ring lug)

nut

split

washer

Battery

Temperature

Sensor

battery

post

CAUTION

:

Ensure nothing is

placed between

the cable ring lug

and the battery post.

5/16-18"

Flange or

Kep nut

battery cable

(with ring lug)

Inverter DC terminal

(5/16 -18" bolt,

5/8" usable length)

CAUTION:

Ensure nothing is

placed between

the DC terminal

and the ring lug.

Figure 2-5, Battery Hardware

Installation

Figure 2-6, Inverter DC Hardware

Installation