beautypg.com

KACO Powador-proLOG User Manual

Page 8

background image

Operating Instructions Powador-proLOG_EN

Page 9

S e c t i o n 4 ·

T e c h n i c a l D a t a

Connections

Powador-proLOG S

Powador-proLOG M

Powador-proLOG XL

Analogue inputs

Number of

1

1

4

DC voltage measurement [V]

0 to 10 (max. 24)

0 to 10 (max. 24)

0 to 10 (max. 24)

DC current measurement [mA]

0 to 20 (max. 40/3 V)

0 to 20 (max. 40/3 V)

0 to 20 (max. 40/3 V)

Resistance measurement

PT1000

PT1000

PT1000

Measuring accuracy

1% of the end value
(0.1 V/0.2 mA)

1% of the end value
(0.1 V/0.2 mA)

1% of the end value
(0.1 V/0.2 mA)

Digital inputs

Number of

1

1

4

S0 pulse input (DC) [V]

Low: 0 to 7
High: 9 to 24

Low: 0 to 7
High: 9 to 24

Low: 0 to 7
High: 9 to 24

Powered exclusively by the unit’s internal power supply

Can be confi gured as a status input

Potential-free contacts

S0 interface specifi cation conforms to DIN 43864

Digital output

Number of

1

1

1

S0 optocoupler (DC)

Max. 70 V/50 mA

Max. 70 V/50 mA

Max. 70 V/50 mA

Display elements

4 LEDs

4 LEDs

4 LEDs

Interfaces

Can be confi gured as an alarm or pulse output

Observe the polarity

Communication

Ethernet

100 MBit (RJ45)

100 MBit (RJ45)

100 MBit (RJ45)

Analogue modem (PSTN)*

1 (RJ12)

-

1 (RJ12)

ISDN modem*

-

-

1 (RJ12)

GSM/GPRS modem

-

-

SIM card slot
Antenna (FME)

*Depending on Powador-proLOG variant

This manual is related to the following products: