9.3.1 Basic principle of monitoring

A relationship between irradiance and generated energy is
used for the physical basis. Ideally, this means that:

[generated power] = [irradiance * area of module * eta
module * eta inverter]

For PV modules with a degree of effi ciency of 12%, an inverter
degree of effi ciency of 91%, and a module area of 10 m², the
idealised relationship can be displayed as follows:

In reality, this relationship is not exactly linear across the entire
range (lower irradiance => lower degree of effi ciency). There-
fore, a solution must be found for a working fault message cri-
terion. For this purpose, a range is “stretched” so that meas-
ured values can move. This requires two linear equations that
defi ne the upper and lower limits of the “plausible” range:

In order to allow the maximum amount of fl exibility in select-
ing the range, two different slopes can be defi ned. The dis-
placement of the linear slopes by tHigh and tLow is specifi ed
as an absolute quantity (e.g. 0.2 kW).

0

0,1

0,2

0,3

0,4

0,5

0,6

0,7

0,8

0,9

1,0

1,1

Gmod [W/m²]

P

ac

[kW]

0

100

200

300

400

500

600

700

800

900

1000 1100

Pac = Gmod * eta mod * eta WR * area

-0,4

-0,2

0

0,2

0,4

0,6

0,8

1,0

1,2

1,4

Gmod [W/m²]

P

ac

[kW]

0

100

200

300

400

500

600

700

800

900 1000

6

5

4

3

2

1

The equations for the linear slopes can now be written as fol-
lows:

Lower limit:

Upper limit:

where: mlow

= 0.85 tlow = - 0.25

mhigh

= 1.1 thigh = 0.15

9.3.2 Setting parameters for the measuring

device

Settings are made in: Admin monitoring -> Formulas -> Cri-
terion x”)

First make the basic settings for this alarm criterion.

Designation: “Power by irradiance”

Status.“Active”

Time: “Interval”

Alarm destination: “Standard contact”

Message type: E-mail

Delay: “8”

(This sets a measuring interval of 15 minutes and an alarm
delay of two hours)

The formula entries are then as follows:

Y

Generation for photovoltaic system (dig_0)

m (lower

limit)

0.85

m (upper

limit)

1.1

x

Irradiance of module

(ana_0); System area; *eta PV;*eta inverter;*

c (lower

limit)

200

c (upper

limit)

200

S e c t i o n 9 ·

C o n f i g u r a t i o n E x a m p l e

Y <

m

lower

X

t

lower

Pac <

m

lower

(G

Module

A

Arry

η

PV

η

INV

) (t

lower

P

nom

)

Y >

m

upper

X

t

upper

Pac >

m

upper

(G

Module

A

Arry

η

PV

η

INV

) (t

upper

P

nom

)

ATTENTION

To send an alarm message, you have to specify the con-
tact for the alarm destination in“Admin monitoring ->
Contact addresses -> Contact x”).