5.4.8 Digital output D0

The digital output can be used as an alarm output to control
signalling devices or as a pulse output to connect a display.

Powador-proLOG M/XL

Powador-proLOG S

Connecting a display to D0

Connecting a signalling device to D0

5.4.9 Analogue/digital

inputs

The unit is equipped with four (XL) or one (S, M) analogue
input(s), which are designed for a voltage measurement of 0
to 10 V.

Powador-proLOG XL

Powador-proLOG S

Counter pulses (maximum frequency: 14 Hz) can be recorded
using four (XL) or one (S, M) digital counter input(s). An inter-
face in accordance with the S0 specifi cation must be available.

Powador-proLOG XL

Powador-proLOG S

S e c t i o n 5 ·

I n s t a l l a t i o n

NOTE

To confi gure this function, connect to the Powador-pro-
LOG and make the required settings via -> “Admin moni-
toring > Switching output” in your browser.

ATTENTION

The output is designed as an optocoupler output (N/O
contact) and must therefore be connected to an external
voltage supply, if necessary. The maximum load is 50 mA.

NOTE

The analogue inputs can be optionally converted for
current measurement or resistance measurement.
You do this in the confi guration menu of the Powador-
proLOG (Admin-Messung -> Admin measurement > Ana-
logue channels).

ATTENTION

Incorrect polarity or using an external voltage supply
greater than 24 V can destroy the measuring input. The
24-V supply is available starting at terminal DI+.

ATTENTION

Incorrect polarity or using a voltage supply greater than
12 V can destroy the measuring input.

NOTE

The digital inputs can be optionally converted for status
evaluation.
This means that the Powador-proLOG can evaluate
switching states 0 or 1 (N/C or N/O contact).
This must be set up using the confi guration fi les
for the Powador-proLOG.
Please contact the KACO new energy hotline.

Powador-proLOG

+ -

D0
+ -

24V
+ -

Signalgeber

Powador-proLOG

Impulseingang

Anzeigedisplay

Powador-proLOG

D0
+ -

+ -

Powador-proLOG

Display