5 Trial Operation (Checking Linear Servomotor Operation)
5.5.3 Troubleshooting for Polarity Detection Errors
5-22
3
Polarity detection
uncompleted
(A.C52)
Model> • The /PDET signal was not input. • Polarity detection was not yet complete. Input the /PDET signal. Model/Command Option Attachable Type> been turned ON under the following circumstances. • An absolute linear scale is being used. • The polarity detection selection for the absolute linear scale was set to not execute. (Pn587.0=0) • Polarity detection was not yet complete. If you are using an absolute linear scale, do one of the following. • Execute polarity detection (Fn080) absolute linear scale. 4 Out of range for polarity detection (A.C53) The movement distance during detection exceeds the range set for Pn48E. An alarm occurs when the motor movement distance during detection becomes out of the range set for Pn48E. If the command distance has not been changed from the factory set value, the motor might have been moved for some reason. Check for the cause and take a proper measure. 5 Polarity detection error 2 (A.C54) An external force was applied to the linear servomotor. Increase the value of the polarity detection confirmation force reference (Pn495). Increase the value of the polarity detection allowable error range (Pn498). (Note that increasing the allowable error will also increase the servomotor temperature.) (cont’d) No. Problem Cause Correction
The servo has
• Set Pn587.0 to 1 to execute polarity detection for an