Programming 5 - 60
H3-08 Terminal A2 Signal Level
H3-08 is one of the special parameter settings required by the Bypass logic circuit. See Table 5.2.
The H3-08 parameter (Terminal A2 Signal Level) allows the programmer to specify the signal that will be applied to the A2
analog input. The A2 analog input can accept either a 0–10 Vdc or 4-20 mA signal as a reference. The Drive also has a DIP
switch (S1) on the removable terminal board that must be set for the proper reference signal into the A2 analog input. The
S1-2 dipswitch setting determines the internal resistance of the A2 input while parameter H3-08 determines how the Drive
interprets the measured signal.
Fig 5.28 DIP Switch S1
Setting
Description
0
0 - 10VDC
2
4 - 20mA (Default)
Table 5.17 DIP Switch S1
Name
Function
Setting
S1-1
RS-485 and RS-422 terminating resis-
tance
OFF: No terminating resistance (Factory default)
ON: Terminating resistance of 110
Ω
S1-2
Input method for analog input A2
OFF: 0 to 10 V (internal resistance: 20 k
Ω)
ON: 4 to 20 mA (internal resistance: 250
Ω) (Factory default)
S1
O
1
Terminating
resistance
DIP Switch S1-1 located on
terminal board.
2