Fig 5.4 dc injection braking to stop, Fig 5.5 coast to stop with timer, Programming 5 - 14 – Yaskawa E7B Drive Bypass User Manual
Page 108

Programming 5 - 14
2:DCInj to Stop: When the Run command is removed, the Drive will Baseblock (turn off its output) for the Minimum Base-
block Time (L2-03). Once the Minimum Baseblock Time has expired, the Drive will inject DC current into the motor wind-
ings to lock the motor shaft. The stopping time will be reduced as compared to Coast to Stop. The level of DC Injection
current is set by parameter b2-02 (50% Default). The DC Injection brake time is determined by the set value in b2-04 and the
output frequency at the time the Run command is removed.
Fig 5.4 DC Injection Braking to Stop
3:Coast w/Timer: When the Run command is removed, the Drive will turn off its output and the motor will coast to a stop. If a
Run command is input before time T (Operation Wait Time) expires, the Drive will not run and the Run command will need
to be cycled before operation can occur. The time T (Operation Wait Time) is determined by the output frequency when the
Run command is removed and the active deceleration time (C1-02).
Fig 5.5 Coast to Stop with Timer
IMPORTANT
If an overcurrent (OC) fault occurs during DCInj to Stop, lengthen the Minimum Baseblock Time (L2-03)
until the fault no longer occurs.
04)
-
(E1
Frequency
Maximum
Frequency
Output
10
04)
-
(b2
Time
Brake
Injection
DC
×
×
=
ON
OFF
Run Command
Output Frequency
Drive Output Voltage Interrupted
DC Injection Brake
DC Injection Brake Time
Minimum Baseblock
Time (L2-03)
100 %
0 %
DC
In
je
cti
on
B
ra
ke
Ti
me
b2-04 x 10
b2-04
10%
100% (Maximum
Output Frequency)
b2-04
(CLOSED)
(OPEN)
Run Command
Output Frequency
Drive Output
Voltage
Interrupted
OFF
ON
Timer Value T
(C1-02)
100 %
0 %
O
pe
rat
ion Wait
Time (
T
)
Deceleration
Time (C1-02)
Minimum
Baseblock
Time (L2-03)
Minimum
Output
Frequency
100% (Maximum
Output
Frequency)
Output Frequency at Stop Command Input
Ignored
Run Command
Timer Value T
(OPEN)
(CLOSED)