E2 motor setup, E2-01 motor rated current, Programming 5 - 50 – Yaskawa E7B Drive Bypass User Manual
Page 144

Programming 5 - 50
E2 Motor Setup
E2-01 Motor Rated Current
Setting Range:
Model Dependent (see appendix B)
Factory Default: Model Dependent
The Motor Rated Current parameter (E2-01) is necessary information for the Drive motor protection function. The motor
overload protection parameter L1-01 is enabled by default. In addition, motor rated current is used by the torque compensation
function to insure optimum torque production. Set E2-01 to the full load amps (FLA) value stamped on the motor’s
nameplate. During Auto-tuning, it is required for the operator to enter the motor rated current in parameter T1-04 on the
Auto-Tuning menu. If the Auto-tuning operation completes successfully, the value entered into T1-04 will be also written into
E2-01.
For applications employing a Drive that is oversized for the motor, E2-01 may be set as low as 10% of the Drive output current
rating. The ampere value in E2-01 however, must always be greater than the “No Load Current” value in parameter E2-03 or
an OPE02 error will be displayed.
Table 5.11 V/f Pattern Default Settings for Drive Capacity 50 to 150 HP for 230V (Continued)
Parameter
No.
Name
Unit
Factory Setting
E1-03
V/f Pattern Selection
–
8
9
A
B
C
D
F
E1-04
Max. Output
Frequency
Hz
50.0
50.0
60.0
60.0
90.0
120.0
60.0
E1-05
Max. Output Voltage
V
240.0
240.0
240.0
240.0
240.0
240.0
240.0
E1-06
Base
Frequency
Hz
50.0
50.0
60.0
60.0
60.0
60.0
60.0
E1-07
Mid. Output
Frequency A
V
2.5
2.5
3.0
3.0
3.0
3.0
3.0
E1-08
Mid. Output
Voltage A
V
17.2
23.0
17.2
23.0
13.8
13.8
13.8
E1-09
Min. Output
Frequency
Hz
1.3
1.3
1.5
1.5
1.5
1.5
1.5
E1-10
Mid. Output
Voltage
V
8.0
10.3
8.0
12.6
6.9
6.9
6.9
E1-11
Mid Output Frequency B
Hz
0
0
0
0
0
0
0
E1-12
Mid Output Voltage B
V
0
0
0
0
0
0
0
E1-13
Base Voltage
V
0
0
0
0
0
0
0
For 480V class units, the value is twice that of 240V class units.