55 table 38: object content (continued) – Yaskawa DeviceNet Option Card CM059 User Manual
Page 55

55
Table 38: Object Content (continued)
01
15
High Speed Limit
Drive Frequency Reference upper limit value is
set/read.
*2 *3
Min. :Unit: [r/min/2
SS
]
where SS: Speed scale: attribute 16
0-
100.0%
0x0708
(1800r/
m)
o
o
Word
16
Speed Scale
Data unit coefficient regarding speed is set/read.
Min. Unit: 1 [r/min]×1/2
SS
where SS: Speed scale setting value
-15-15
(F1-0F)
00
o
o
Byte
17
Current Scale
Data Coefficient regarding current is set/read.
Current Unit: 0.1 [A]×1/2
CS
where CS: Current scale setting value
-15-15
(F1-0F)
00
o
o
Byte
1A
Power Scale
Data Coefficient regarding power is set/read.
Power Unit: 1 [W]×1/2
PS
where PS: Power scale setting value
-15-15
(F1-0F)
00
o
o
Byte
1B
Voltage Scale
Data unit coefficient regarding voltage is set/
read.
Voltage Unit: 1 [V]×1/2
VS
where VS: Voltage scale setting value
-15-15
(F1-0F)
00
o
o
Byte
1C
Time Scale
Data unit coefficient regarding time is set and
read.
Time Unit: 1 [ms]×1/2
TS
where TS: Time scale setting value
-15-15
(F1-0F)
00
o
o
Byte
1D
Ref From Net
Drive frequency reference input selection status
is displayed
*1
00: Frequency Reference input other than
DeviceNet is enabled.
01: Frequency Reference input from DeviceNet
is enabled.
00,01
00
o
−
Byte
Notes:
*1 A setting during drive operation cannot be changed.
*2 An application of speed command, speed monitor, speed lower limit value, and speed upper limit value must be set
as a motor pole value (2~39) to the drive parameter o1-03 (frequency reference set/display unit selection)
*3 Control mode, speed lower limit, and speed upper limit cannot be set during drive operation.
SS: Speed Scale (AC/DC Drive Object Attr. 22)
CS: Current Scale (AC/DC Drive Object Attr. 23)
PS: Power Scale (AC/DC Drive Object Attr. 26)
VS: Voltage Scale (AC/DC Drive Object Attr. 27)
TS: Time Scale (AC/DC Drive Object Attr. 28)