Option Indication LEDs

The table below describes the function of DeviceNet specific LEDs.

Table 11: DeviceNet LED Function

LED

Name

Display

Operation Status

Description

Color

Status

MS

Green

Lit

During option operation

The option is operating normally.

Green

Flashing During option preparation

Initial setting status or communication is not ready.

Red

Lit

Recovery from fault
impossible

Impossible recovery fault occurred in the option.

Red

Flashing Recovery from fault possible

Possible recovery fault such as switch settings occurred.

Not lit

Power OFF

Power is not being supplied to the drive.
the option has not been properly connected. Therefore, the
power is not being supplied to the option.

NS

Green

Lit

Online communication is
taking place

DeviceNet is communicating normally.

Green

Flashing

Online communication is not
taking place.

DeviceNet network is normal, but is not communicating
with the master.

Red

Lit

Communication fault

A fault that makes it impossible for the DeviceNet to
communicate has occurred.

„ MAC ID overlap
„ Bus-off detection

Red

Flashing Communication timeout

Communication time out with master occurred.

Not lit

Offline, Power OFF

DeviceNet is not set to online.
Power is not being supplied to the option.
Mismatch of baud rate.

PWR

Green

Lit

Power ON

Power to the option is supplied from the drive.

Not lit

Power OFF

Power is not being supplied to the drive.
The option has not been properly connected. Therefore, the
power is not supplied to the option.

WD

Green

Flashing During CPU operation

CPU of the option is operating normally.

Red

Lit

CPU fault

Option CPU is being ready or has fault.

Not lit

Power OFF

Power is not being supplied to the drive.
The option has not been properly connected. Therefore,
power is not being supplied to the option.

Notes:
1) If the baud rate configuration is set for “Not Allowed”, both the NS and MS diagnostic LEDs will be solid RED.
2) The LEDs will flash red once (100 ms) during initialization (Internal testing process to verify that the red LED is working properly).