4 Drive Change Summary
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
9
4
Drive Change Summary
Overview
The following is an overview of changes made the drive with software PRG: 0035 and PRG: 0036.
Drive Software Changes
Table 2 Parameter Enhancements for PRG: 0035
Table 3 Digital Input H1- Enhancements for PRG: 0035
Table 4 Digital Output H2- Enhancements for PRG: 0035
Table 5 Added H3-09 Analog Input Function for PRG: 0035
Parameter
Description
Page
A1-01 Language Selection Selection 6:Portuguese is removed.
A1-03 Initialization Mode Added selection 7770:General Purpose.
b1-01 Frequency
Reference Selection
Added selection 5:Geothermal Mode.
b1-03 Stop Method
Default changed from: Ramp to Stop (0) to Coast to Stop (1).
C6-02 Carrier Frequency
Default value changed to setting 1 (2.0 kHz) for all drive sizes.
P8-01 Water Lev./Suc.
Pres. Selection
Selection 1: Changed from Enabled to Water Level Control.
Added selection 2:Suction Pressure Control.
P8-09 Low Level Behavior Added selection 3:Auto-Restart (time set by P8-12).
P9-01 Lead Drive
Selection
Added selection 2:Stop History.
P9-05 Lag Drive Mode
Added selection 3:Follow Lead Speed.
P9-08 Add Pump Mode
Added selection 3:Flow Meter.
P9-12 Remove Pump
Mode
Added selection 3:Flow Meter.
P9-23 Max Pumps
Running
Range changed from 1 - 16 to 1 - 8.
Default changed from 16 to 8.
–
P9-25 Highest Node
Address
Range changed from 2 – 16 to 2 - 8.
Function
Description
Page
72 Remote Drive Disable
Digital Input function (normally open or normally closed) that can be used to prevent the
drive from running with a programmable delay time.
Function
Description
Page
4A Transducer Loss <1>
<1> Modified from previous version.
Closed: During a “Feedback Loss” alarm.
Closed: During a “FBL – Feedback Loss” fault”.
Closed: During an “A1-LOST Terminal A1 Lost” alarm. <1>New
Closed: During an “A1-LOST Terminal A1 Lost” fault. <1>New
57 Low Water Level <1>
This will energize if P8-01 = 1 and the level in the well drops below the Low Level
Detection Level (P8-07) for more than the Low Level Detection Delay Time
(P8-08), or if there is a LOWWL – Low Water Level Fault.
58 Low Suction Level
This will energize if P8-01 = 2 and the suction pressure drops below the Low Suction
Pressure Detection Level (P8-07) for more than the Low Suction Pressure Delay Time
(P8-08), or if there is a LOSUC – Low Suction Pressure Fault.
Function
Description
Page
20 Geothermal Mode
Temperature input for geothermal mode operation.