Yaskawa iQpump Manual Supplement User Manual
Page 86

86
YASKAWA TM.iQp.10 Technical Manual Supplement
zP9-50
<0034>
0878
Water Level Source
Water Lvl Source
Defines which signal to use for Water Level Control (P8-) when P1-01
= 3.
0: Analog Only
1: Ana->Net, No Alrm
2: Ana->Net, Alarm
3: Network Only
Setting has no effect when P1-01
≠
3
0 ~ 3
0
Programming
P9-50
<0035>
0878
Suction Pressure Source
Suction Pres Src
Defines which signal to use for Suction Pressure Control (P8-) when
P1-01 = 3.
0: Analog Only
1: Ana->Net, No Alrm
2: Ana->Net, Alarm
3: Network Only
Setting has no effect when P1-01
≠
3
0 ~ 3
0
Programming
P9-99
<0036>
0875
Network Compatibility
Selection
Network Comp Sel
Determines the communication compatibility for the iQpump Memobus
Network
0: A-Version 30034
Use this mode if (ONE or MORE) iQpump Controllers on the network
have software version monitor U1-14=30034 and nameplate PRG: 0034.
1: B-Version 30035+
Use this mode if (NONE) of the iQpump Controllers on the network have
software version monitor U1-14=30034 and nameplate PRG: 0034.
0 ~ 1
1
Programming
Auto-Tuning
T1-02
0702
Motor Rated Power
Mtr Rated Power
Sets the motor rated power in kW.
Note: T1-02 should be left at the default value (last 3 digits of the drive
model number).
0.00 ~
650.0
kVA
Dependent
Auto-Tuning
T1-04
0704
Motor Rated Current
Rated Current
Sets the motor rated current. (Used only during an auto-tune.)
kVA
Dependent
kVA
Dependent
Auto-Tuning
Denotes that parameter can be changed when the drive is running.
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location