22
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
Figure 4
Figure 4 Digital Operator Display Showing Geothermal Mode Operation
Parameter No.
Parameter Name
Description
Range
Default
P4-33
Minimum Geothermal Speed
Sets the frequency reference characteristics based on the set
temperature points and the corresponding frequency.
For proper operation, P4-34 > P4-33 and P4-38 > P4-37 > P4-36 >
P4-35.
Geothermal Mode Frequency/Temperature Characteristic|
(Normal Operation)
.
Geothermal Mode Frequency/Temperature Characteristic
(Inverse Operation)
0.00 ~
120.00 Hz
40.00 Hz
P4-34
Maximum Geothermal Speed
0.00 ~
120.00 Hz
40.00 Hz
P4-35
Low Temperature to Run at
Maximum Geothermal Speed
-110.0 ~
450.0 °F
55.0 °F
P4-36
Low Temperature to Run at
Minimum Geothermal Speed
-110.0 ~
450.0 °F
65.0 °F
P4-37
High Temperature to Run at
Minimum Geothermal Speed
-110.0 ~
450.0 °F
75.0 °F
P4-38
High Temperature to Run at
Maximum Geothermal Speed
-110.0 ~
450.0 °F
85.0 °F