YASKAWA TM.iQp.10 Technical Manual Supplement
P9-08
<0034>
0887
Add Pump Mode
Add Pump Mode
Selects the detection method for staging a new pump:
0: Output Frequency
1: Feedback
2: Feedback + Fout
3: Flow Meter <0035>
0 ~ 3
0
Programming
P9-09
<0034>
0888
Add Freq Level
Add Freq Lvl
When P9-08 = 0 and the output frequency rises above this level for the
time set in P9-11, the lead drive will request for a new lead drive through
the iQpump Memobus Network.
When P9-08 = 2 and the output frequency rises above this level the delta
feedback (setpoint - feedback) has exceeded the level set in
P9-10 for the time set in P9-11, the lead drive will request for a new lead
drive through the iQpump Memobus network.
0.0 ~
120.0 Hz
56.0 Hz
Programming
P9-10
<0034>
088A
Add Delta Level
Add Delta Lvl
When P9-08 = 1 and the delta feedback (setpoint - feedback) has exceeded
this level for the time set in P9-11, the lead drive will request for a new
lead drive through the iQpump Memobus Network.
When P9-08 = 2 and the delta feedback (setpoint - feedback) has exceeded
this level and the output frequency is above P9-09 for the time set in P9-11,
the lead drive will request for a new lead drive through the iQpump
Memobus network.
0 ~ 6000.0
(system
units
P1-02)
0.0 (system
units
P1-02)
Programming
P9-11
<0034>
088A
Add Delay Time
Add Dly Time
Delay time before a new lead drive is added to the system.
0 ~ 3600
sec
10 sec
Programming
P9-12
<0034>
088B
Remove Pump Mode
Remove Pump Mode
Selects the detection method for de-staging to the previous lead pump:
0: Output Frequency
1: Feedback
2: Feedback + Fout
3: Flow Meter <0035>
0 ~ 3
0
Programming
P9-13
<0034>
088C
Remove Freq Level
Remove Freq Lvl
When P9-12 = 0 and the output frequency drops below this level for the
time set in P9-15, the lead drive will request to be removed from the
system through the iQpump Memobus network.
When P9-12 = 2 and the output frequency drops below this level and the
delta feedback (feedback - setpoint) has exceeded the level set in P9-14 for
the time set in P9-15, the lead drive will request to be removed from the
system through the iQpump Memobus network.
0.0 ~
120.0 Hz
40.0 Hz
Programming
P9-14
<0034><0034
>
088D
Remove Delta Level
Remove Delta Lvl
When P9-12 = 1 and the delta feedback (feedback - setpoint) has exceeded
this level for the time set in P9-15, the lead drive will request to be
removed from the system through the iQpump Memobus network.
When P9-12 = 2 and the delta feedback (feedback - setpoint) has exceeded
this level and the output frequency is below P9-13 for the time set in P9-
15, the lead drive will request to be removed from the system through the
iQpump Memobus network.
0 ~ 6000.0
(system
units
P1-02)
0.0 (system
units
P1-02)
Programming
P9-15
<0034>
088E
Remove Delay Time
Remove Dly Time
Delay time before the lead drive is removed from the system.
0 ~ 3600
sec
10 sec
Programming
P9-16
<0034>
088F
Stabilization Time
Stabilization Time
Time used to stabilize the system when a pump is staged or de-staged.
Lead-lag control and pump protection is suspended during this time.
0 ~ 3600
sec
3 sec
Programming
Denotes that parameter can be changed when the drive is running.
P9-17
<0034>
0890
Setpoint Modifier
Set-pt Modifier
System Set-point is incremented with this value depending on the number
of pumps running.
Pump 1: Set-point
Pump X: Set-point + {(X-1) (P9-17)}
-6000.0 ~
6000.0
(system
units
P1-02)
0.0 (system
units
P1-02)
Programming
P9-18
<0034>
0891
High Feedback Quick De-
Stage
High FB De-stage
Determines the feedback level to trigger a quick de-stage, set as a
percentage of parameter P1-09. The quick de-stage ignores parameters P9-
12 to P9-15 and only uses an internal 2 second delay.
0.0 ~
100.0 %
90.0 %
Programming
P9-19
0892
Alternation Unit
Alternation Unit
Selects the unit for P9-03
0: Hours (hr)
1: Minutes (min)
0 ~ 1
0
Programming
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location