YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
11 Improved and Miscellaneous Functions
11
Improved and Miscellaneous Functions
Terminal A1 Loss Detection
Feedback loss detection alarm and fault messages are enhanced to differentiate between terminal A1 feedback loss and
Terminal A2 PI feedback loss.
Use parameter b5-12 is select feedback loss detection operation for terminal A1.
Parameters
b5-12 Feedback Loss Detection
New Alarm Message: Feedback Loss Terminal A1 (Modified)
New Fault Message: Feedback Loss Terminal A1 (Modified)
Multi-function Output Setting: Transducer Loss (Modified)
Function Description Feedback Loss Detection
Wire break (feedback loss detection) will be detected on Terminal A1 when all of the following conditions are satisfied:
• PI Feedback Loss Detection is enabled (b5-12 = 1 or 2).
• PI function is enabled (b5-01 > 0).
• Dual Zone PI or Water Level/Suction Pressure Control is enabled (b5-01 = 2 or P8-01 > 0, P1-01 = 0, b5-09 = 0, and
H3-09 = B).
• PI function is NOT disabled via Multi-Function Digital Input.
• Signal on Terminal A1 falls below -6.25 % or rises above 106.25 % for more than 1 second.
Note: Wire-break detection on Terminal A1 is checked after the gain/bias parameters (H3-02 and H3-03) are applied.
Setting
Description
0
Disabled
1
Alarm
2
Fault (factory default)
Fault Display
Description
A1-LOST
Terminal A1 Lost
Shown when b5-12 = 1 and feedback signal on terminal A1 is lost. Check to ensure the device connected to
Terminal A1 is installed and working properly.
Fault Display
Description
A1-LOST
Terminal A1 Lost
Shown when b5-12 = 2 and feedback signal on terminal A1 is lost. Check to ensure the device connected to
Terminal A1 is installed and working properly.
Setting
Description
4A
Transducer Loss
Closed: During a "Feedback Loss" alarm.
Closed: During a "FBL - Feedback Loss" fault".
Closed: During an "A1-LOST Terminal A1 Lost" alarm (New)
Closed: During an "A1-LOST Terminal A1 Lost" fault (New)