4 Drive Change Summary
10
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
Table 6 Additional or Modified Fault Codes for PRG: 0035
Table 7 Additional Alarms or Messages for PRG:0035
Table 8 Additional Alarms or Messages for PRG:0036
Fault Code
Description
Page
OPE13
Terminal A1
Displayed when terminal A1 is assigned to more than one function. OPE13 is modified from
the previous software version PRG:0034.
OPE17
Run/Stp-CoastTmr
Displayed when Run/Stop Control and Coast To Stop w/Timer are both enabled.
OPE18
Net Incompatible
Displayed when using features specific to iQpump software version 30035+ and nameplate
PRG: 0035 or greater with parameter P9-99 set to (0: A:Version 30034).
OPE19
Geothermal Set
Displayed when a parameter selection is not compatible with the Geothermal Mode
(b1-01 = 5) setting.
Temp Lost
Geothermal Input
Displayed when geothermal input is not present.
LOSUC
Low Suction
Suction pressure is below programmed level.
Alarm
Description
Page
Net FlowMeter
Lost, Chk Source
Displayed when there is no drive on the Memobus Network with an analog Flow Meter.
LOSUC
Low Suction
Displayed when Low City Pressure is active and alarm selection P4-27 = 1.
Low Water
in Tank
Displayed when Low City Pressure is active and alarm selection P4-27 = 2.
Temp Lost
Geothermal Input
Displayed when a geothermal input is not present.
R-DNE-S <1>
Remote Drv Dis
<1> The character is a place holder for the actual digital input designation, such as S1, S2, or S3.
Remote drive disable is active.
AnalogA1 Lost
Switched to Net
Displayed when there is a defective or broken analog input source. Analog Terminal A1 has
not been detected, and the Network Water Level or Suction Pressure signal is now used.
Net Wtr/Suctn
Lost, Chk Source
Displayed when a valid analog source for Water Level or Suction Control Pressure can not be
found on the network.
Alarm
Description
Page
OPE20
Net WL/SP Mode
Incompatible Network Water Level / Suction Pressure Mode.
-
Low WL/SP
Drive Disabled
Drive is unable to run because the Water Level or Suction Pressure is below the P8-05 setting.
-