YASKAWA TM.iQp.10 Technical Manual Supplement
P1-09
0608
High Feedback Level
High FB Level
The drive will display a “High Feedback Level (HFB)” alarm when the
feedback level rises above the programmed level. The alarm will turn off
when the feedback level falls below the programmed High Feedback Level
minus the Hysteresis Level (P1-13). This function is active during running
in the hand mode, auto mode, pre-charge and thrust-bearing mode.
If P1-01 = 3, parameter P9-18 uses this value to calculate the quick de-
stage feedback level.
<0034>
0.0 ~
6000.0
(system
units
P1-02)
155.0
(system
units
P1-02)
Programming
P1-10
0609
High Feedback Level Fault
Delay Time
Hgh Lvl Flt Time
The drive will initiate a “High Feedback Fault (HFB)” when the feedback
level rises above the programmed level for a time specified in P1-10. The
drive will coast to a stop when a fault occurs. This function is active during
running in all operation modes.
If P1-01 = 3, the function will stop all drives running on the network when
the system fault occurs.
<0034>
0 ~ 3600
sec
2 sec
Programming
P1-11
<0032>
0106
Maximum SetPoint
Difference
Max Set-point Diff
When the drive is running and the difference between the setpoint and the
feedback exceeds the level in P1-11 for the time specified in P1-12, the
drive will trip on a “Not Maintaining Set-point (NMS)”. The drive will
coast to a stop when a fault occurs. A value of 0 disables this function. This
function is only active during running while operating in auto mode.
If P1-01 = 3, the function is active on the lead drive, but will stop all drives
running on the network when the system fault occurs.
<0034>
0.0 ~
6000.0
(system
units
P1-02)
0.0 (system
units
P1-02)
Programming
P1-12
<0032>
0107
Not Maintaining Set-point
Time
Not Maint SP Tm
Delay time before a Not Maintaining Set-point fault occurs. Pump
protection criteria specified in P1-11 must be met for the drive to fault. The
drive will coast to a stop when a fault occurs. A value of 0 disables Not
Maintaining Set-point fault.
0 ~ 3600
sec
60 sec
Programming
P1-13
0108
Hysteresis Level
Hysteresis Level
Hysteresis Level used for low and high feedback alarm detection. See
function P1-07 and P1-09.
0.0 ~ 100.0
(system
units
P1-02)
0.0 (system
units
P1-02)
Programming
P1-14
0109
Prime Loss Level
Prime Loss Level
Used to detect loss of prime in the pump. If output current drops below this
level for the time specified in P1-12 and the output frequency is at fmax, a
“Loss Of Prime” fault occurs. The drive will coast to a stop when a fault
occurs.
If P1-01 = 3, the function is active on the lead drive, but will stop all drives
running on the network when the system fault occurs.
<0034>
0.0 ~
1000.0 A
0.0 A
Programming
P1-15
010A
Low/Hi Water Digital
Input Configuration
Water DI Config
<0034>
Sets the type of control operation
0: Low N.O. - Hi N.O. (Low Water Normally Open, High Water Normally
Open)
<0034>
1: Low N.C. - Hi N.O. (Low Water Normally Closed, High Water
Normally Open)
<0034>
2: Low N.O. - Hi N.C. (Low Water Normally Open, High Water Normally
Closed)
<0034>
3: Low N.C. - Hi N.C.(Low Water Normally Closed, High Water Normally
Closed)
<0034>
To use the low water function one of the digital inputs (H1-=85) must
be programmed. The low water input can be used for a low water condition
or in combination with the pre-charge function to indicate the reservoir is
filled. The low water input fault is only active during running while
operating in auto mode.
0 ~ 3
0
Programming
P1-16
<0034>
87F
Loss of Prime Time
Prime Loss Time
Delay time before a Loss of Prime fault occurs. Pump protection criteria
specified P1-14 must be met for the drive to fault. On fault the drive will
coast to a stop.
1 ~ 600 sec
20 sec
Programming
Denotes that parameter can be changed when the drive is running.
Pump Protection
P2-01
060A
Sleep Level Type
Sleep Lvl Type
Sets the sleep type.
0: Output Frequency
1: Output Current
2: Feedback
3: Output Speed (rpm)
<0034>
4: Low Flow (Terminal A1 - Flow meter required)
<0034>
Note: Feedback depends on PID direction operation.
Displays a “Sleep” Alarm when active.
0 ~ 4
0
Programming
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location