Initialization for basic applications (a1-03) – Yaskawa iQpump Manual Supplement User Manual
Page 38

11 Improved and Miscellaneous Functions
38
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
Initialization for Basic Applications (A1-03)
A new initialization mode setting 7770 is available under parameter A1-03 (Initialize Parameters). This setting allows
users to easily configure the iQpump Controller for use as a standard drive in simple applications. In this mode the
iQpump Controller defaults to start/stop operation from the terminals and speed control using a 0-10 Vdc signal to analog
input A1.
A1-03 Initialize Parameters
The Table below shows the default parameters settings for the standard iQpump Controller 2-wire initialization (2220)
and the General Purpose Initialization (7770).
Parameters Modified for General Purpose Initialization
Note: After performing a General Purpose initialization (7770), the parameters shown in this table will be visible in the Modified
Constants menu, with the exception of parameters marked by *.
Setting
Description
0
No Initialize (factory default)
1111
User Initialize
The modified iQpump Controller parameters are returned to the values selected as user settings. User
settings are stored when parameter o2-03 = 1: Set Defaults.
2220
2-Wire Initialize
Initializes the iQpump Controller for 2 Wire Control Operation
3330
3-Wire Initialize
Initializes the iQpump Controller for 3 Wire Control Operation
7770
General Purpose
Configures the iQpump Controller for General Purpose Operation
Parameter No.
Parameter Name
Factory Default Setting
Setting After General
Purpose Initialize
(A1-03 = 7770)
b1-01
Frequency Reference Selection 0 (Operator)
1 (Terminals)
b1-02
Run Command Selection
0 (Operator)
1 (Terminals)
b5-01
PID Mode Setting
1 (Enabled)
0 (Disabled)
C1-01
Acceleration Time 1
20.0 sec
25.0 sec
C1-02
Deceleration Time 1
10.0 sec
25.0 sec
C6-02
Carrier Frequency Selection
1 (2.0 kHz)
kVA dependent
H1-04
Terminal S6 Selection
80 (Hand Mode)
4 (Multi-Step SP 2)
H1-05
Terminal S7 Selection
84 (Disable Pre-Charge)
F (Term Not Used)
H2-01
Terminal M1-M2 Selection
40 (Pump 2 Control)
0 (During Run 1)
H2-02
Terminal M3-M4 Selection
41 (Pump 3 Control)
A (Remote/Auto Oper)
H3-09*
Terminal A2 Function Selection B (PID Feedback)
2 (Aux Reference)
L5-01
Number of Auto Restarts
5
0
L5-03
Maximum Restart Time
20.0 sec
180.0 sec
o1-06*
User Monitor Selection Mode
1 (3 Mon Selectable)
0 (3 Mon Sequential)
P1-02
System Units
1 (psi:lb/SqrInch)
14 (Hz: Hertz)
P1-03
Feedback Scaling
145
26000
P1-05
Start Level Delay Time
1 sec
0 sec
P1-06
Minimum Pump Frequency
40.0 Hz
0.0 Hz
P4-05
Thrust Frequency
30.00 Hz
0.00 Hz
P4-11
Utility Delay Time
0.2 minutes
0.0 minutes
P5-02
Hand Reference
40.00 Hz
0.00 Hz