10 iQpump MEMOBUS/Network Operation
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
33
P9-11 Add Delay Time
P9-12 Remove Pump Mode
Selects the detection method for de-staging to the previous lead pump.
P9-15 Remove Delay Time
Alarm: Network Water or Suction Pressure Signal Lost
Range
Description
Default
0 ~ 3600 sec
Delay time before a new lead drive is added to the system.
10 sec
Setting
Description
0
Output Frequency (factory default)
1
Feedback
2
Feedback + Fout
3
Flow Meter
Range
Description
Default
0 ~ 3600 sec
Delay time before the lead drive is removed from the system.
10 sec
Alarm Display
Description
Net FlowMeter
Lost, Chk Source
There is no drive on the Memobus Network with an analog Flow Meter.
Cause: With P1-01 = 3, P6-01 > 0 and P9-40 = 1 (Network), the Flow Meter function needs a valid Flow
Rate from the network originating from another drive that is also running the Flow Meter function
(P6-01 > 0) with P9-40 = 0 (Analog).
Countermeasure: If the drive has an operational Flow Meter connected to Terminal A1, set P9-40 = 0. If
another drive on the Memobus Network has a Flow meter connected to Terminal A1, confirm that drive is
online, with P6-01 > 0 and P9-40 = 0.