YASKAWA TM.iQp.10 Technical Manual Supplement

Pressure and Level Control

zApplies when P8-01 = 0 or 1

„Applies when P8-01 = 2

P8-01

<0034>

860

Water Level/Suction
Pressure Selection
WtrLvl/SuctnPres

Sets the mode of operation for the Water Level/Suction Control function:
0: Disabled
1: Water Level Control
2: Suction Control <0035>

0 ~ 2

0

Programming

zP8-02

<0034>

861

Water Level Scaling
Water Lvl Scale

Sets the full scale (20 mA) output of the pressure transducer connected to
Terminal A1.

5 ~

500 psi

100 psi

Programming

„P8-02

<0035>

861

Suction Transducer
Scaling
Suction Scaling

Sets the full scale (20 mA) output of the pressure transducer connected to
Terminal A1.

5 ~

500 psi

100 psi

Programming

zP8-03



<0034>

862

Water Level Set-point
Water Lvl Setpnt

Sets the amount of water above the sensor that the drive will attempt to
regulate to.

0.0 ~

1200.0 ft

20.0 ft

Programming

„P8-03



<0035>

862

Suction Pressure
Set-point
Suction Setpoint

Sets the amount of suction pressure that the drive will attempt to regulate
to.

0.0 ~

1200.0 psi

20.0 ft

Programming

zP8-04



<0034>

863

Minimum Water Level
Min Water Level

When the amount of water above the sensor drops below this level for
more than the P2-03 time, the drive will go to sleep.

0.0 ~

1200.0 ft

10.0 ft

Programming

„P8-04



<0035>

863

Minimum Suction
Pressure
Min Suction Pres

When the suction pressure drops to below this level for more than the P2-
03 time, the drive will go to sleep and turn off all lag pumps.

0.0 ~

1200.0 psi

10.0 ft

Programming

zP8-05



<0034>

864

Wake-Up Water Level
Wake-Up Level

If the drive has been forced to sleep based upon the minimum water level
(P8-04), the water must go above this level for more than the P8-13 time in
order to wake up.

0.0 ~

1200.0 ft

30.0 ft

Programming

„P8-05



<0035>

864

Wake-Up Suction Pressure
Wake-Up Pres

If the drive has been forced to sleep based upon the minimum suction
pressure (P8-04), the suction pressure must go above this level for more
than the P8-13 time in order to wake up.

0.0 ~

1200.0 psi

30.0 ft

Programming

zP8-06



<0034>

865

Level Control Minimum
Speed
Level Min Spd

This parameter sets the minimum speed the drive will be allowed to run at
when the drive is controlling the water level. When the drive is controlling
pressure or this parameter is set less than P1-06 and P4-05, P1-06 and P4-
05 will be used as the minimum speed.

0.00 ~

120.00 Hz

0.00 Hz

Programming

„P8-06



<0035>

865

Suction Control Minimum
Speed
Suction Min Spd

This parameter sets the minimum speed the drive will be allowed to run at
when the drive is controlling suction pressure. When the drive is
controlling outlet pressure or this parameter is set less than P1-06 and P4-
05, P1-06 and P4-05 will be used as the minimum speed.

0.00 ~

120.00 Hz

0.00 Hz

Programming

zP8-07



<0034>

866

Low Level Detection
Level
Low Level Detection

When the amount of water above the sensor drops below the level for more
than the P8-08 time, the drive will respond depending on the
P8-09 setting.
A setting of 0.0 disables this detection.

0.0 ~

1200.0 ft

0.0 ft

Programming

„P8-07



<0035>

866

Low Suction Pressure
Detection Level
Low Pres Detection

When the amount of suction pressure drops below this level for more than
the P8-08 time, the drive will respond depending on the P8-09 setting. A
setting of 0.0 disables this detection.

0.0 ~

1200.0 psi

0.0 ft

Programming

zP8-08



<0034>

867

Low Level Detection Time
Delay
Low Lvl Det Tm

Sets the amount of time delay that the water level must drop below the P8-
07 level before the drive will react.

0.0 ~

300.0

(P8-14

units)

0.1 min

Programming

„P8-08



<0035>

867

Low Suction Pressure
Time Delay
Low Pres Det Tm

Sets the amount of time delay that the suction pressure must drop below
the P8-07 level before the drive will react. Time unit is defined by P8-14.

0.0 ~

300.0

(P8-14

units)

0.1 min

Programming

zP8-09

<0034>

868

Low Level Behavior
Low Lvl Behavior

Sets how the drive will respond when the water level in the well drops
below the P8-07 level for more than the P8-08 time.
0: No Display (Digital Output Only)
1: Alarm Only
2: Fault
3: Auto-Restart (time set by P8-12)

0 ~ 3

1

Programming

„P8-09

<0035>

868

Low Suction Pressure
Behavior Select
Low Pressure Sel

Sets how the drive will respond when the suction pressure drops below the
P8-07 level for more than the P8-08 time.
0: No Display (Digital Output Only)
1: Alarm Only
2: Fault
3: Auto-Restrart (time set by P8-12)

0 ~ 3

1

Programming

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location