5 Feature Details - Remote Drive Disable
12
YASKAWA TM.iQp.10 iQpump Technical Manual Supplement
Figure 2
Figure 2 Remote Disable: Active to Inactive Operation
P4-25 Remote Drive Disable On-Delay Time
P4-26 Remote Drive Disable Off-Delay Time
Multi-function Input Setting: Remote Drive Disable Function
Alarm: Remote Drive Disable
Note: S or Sx denotes the digital input terminal programmed for this function.
Range
Description
Default
1 - 1000 sec
Sets the amount of time a “Remote Drive Disable” condition needs to be
present before the drive will stop.
0 sec
Range
Description
Default
1 - 1000 sec
Sets the amount of time a "Remote Drive Disable" condition must be absent
before the drive will be allowed to run.
0 sec
Setting
Description
72 Remote Drv Disbl
Remote Drive Disable: Prevents the iQpump Controller from running when active for the time set in
P4-25. Must be inactive for the time set in P4-26 to allow the drive to run again.
Note: Parameter P4-24 determines if this input is Normally Open or Normally Closed.
Alarm Display
Description
R-DNE-Sx
Remote Drv Dis
Multi-function Input Terminal S (H1-0 = 72) has been closed for the time set in P4-25 when P4-24 = 0.
or
Multi-function Input Terminal S (H1-0 = 72) has been open for the time set in P4-25 when P4-24 = 1.
iQpump Drive Enabled
iQpump Drive Stopped
Time
Remote
Drive Disable
Active
P4-26 Off-Delay Time
Inactive