Yaskawa iQpump Manual Supplement User Manual
Page 81

YASKAWA TM.iQp.10 Technical Manual Supplement
81
P6-10
<0034>
849
Accumulation Level
Course
Accum Lvl Course
Sets the accumulated volume that will trigger the Accum Level alarm.
Accum Level fault, or Accum Level digital output. Total Accum Level can
be calculated as follows:
Total Accum Level = P6-10 x 1000 + P6-09.
If P1-01 = 3, an ACCUM fault will stop all drives running on the network.
0 ~
61036 kgl
0 kgl
Programming
P6-11
<0034>
84A
Accumulation Behavior
Accum Behavior
Sets how the drive will respond when the accumulated volume reaches the
P6-09 and P6-10 level.
0: No Display
1: Alarm Only
2: Fault
3: Fault - Auto Flow Accum Reset
0 ~ 3
1
Programming
P6-12
<0034>
84B
High Flow Level
High Flow Level
If the drive is running and the flow goes above this level for more than the
P6-13 time, a High Flow fault or alarm will occur.
A setting of 0 disables the High Flow detection.
If P1-01 = 3, a HIFLO fault will stop all drives running on the network.
0.0 ~
6000.0
(*n1)
0.0
Programming
P6-13
<0034>
84C
High Flow Detection
Delay Time
High Flow Time
Sets the amount of time the flow rate must be above the P6-12 level before
a High Flow condition is detected.
1 ~ 6000
sec
10 sec
Programming
P6-14
<0034>
84D
High Flow Select
High Flow Sel
Sets the behavior of the drive when a “High Flow” condition is detected.
0: No Display
1: Alarm Only
2: Fault
3: Auto-Restart (time set by L5-03)
0 ~ 3
1
Programming
(*n1) Displayed units are determined by parameter P6-02.
Anti-Jam/De-Scale
P7-01
<0034>
84F
Anti-Jam/De-Scale
Operation Selection
Anti-Jam/De-Scale
Selects if the Anti-Jam or De-Scale functions are enabled.
0: Disabled
1: Anti-Jam Enabled
2: De-Scale Enabled.
3: Force De-Scale
0 ~ 3
0
Programming
P7-02
<0034>
850
Anti-Jam/De-Scale Cycle
Count
A-J Cycle Count
This parameter sets the maximum number of cycles attempted before the
Anti-Jam fault occurs and also sets the number of fwd/rev cycles for the
De-Scale function.
1 ~ 100
1
Programming
P7-03
<0034>
851
Anti-Jam Detection
Current Level
A-J Detection Level
Sets the current level (at start) that will trigger the Anti-Jam function. Set
as a percentage of motor rated current.
50 ~ 200 %
120 %
Programming
P7-04
<0034>
852
Anti-Jam Detection Time
A-J Det. Time
Sets the amount of time the current must be above the P7-03 level to
trigger the Anti-Jam function.
0.1 ~ 2.0
sec
0.3 sec
Programming
P7-05
<0034>
853
Anti-Jam/De-Scale
Frequency Reference
AJ/De-Scale Freq
Sets the speed during the De-Scale operation and during reverse operation
of the Anti-Jam function.
0.00 ~
120.00 Hz
25.00 Hz Programming
P7-06
<0034>
854
De-Scale Forward Run
Time
De-Scale Fwd Run
Sets the amount of time the drive will run in the forward time each cycle
during the De-Scale function.
1 ~ 6000
sec
10 sec
Programming
P7-07
<0034>
855
De-Scale Reverse Run
Time
De-Scale Rev Run
Sets the amount of time the drive will run in the reverse time each cycle
during the De-Scale function.
1 ~ 6000
sec
10 sec
Programming
Denotes that parameter can be changed when the drive is running.
P7-08
<0034>
856
De-Scale Acceleration
Time
De-Scale Accel
Sets the amount of time it will take the drive to accelerate from zero to the
De-Scale frequency reference P7-05 (internally limited 0.1 ~ 6000.0 sec).
0.0 ~
600.0 sec
2.0 sec
Programming
P7-09
<0034>
857
De-Scale Deceleration
Time
De-Scale Decel
Sets the amount of time it will take the drive to decelerate from the
De-Scale frequency reference P7-05 to zero (internally limited 0.1 ~
6000.0 sec).
0.0 ~
600.0 sec
2.0 sec
Programming
P7-10
<0034>
858
De-Scale Pump Run Time
De-Scale Time
Sets the number of pump operating hours (pump speed > 0) before a
De-Scale routine will run.
1.0 ~
2000.0 hr
168.0 hr
Programming
P7-11
<0034>
859
Anti-Jam Release Time
Anti-Jam Release
Sets the amount of time that the current must be below the P7-03 level in
order to resume normal operation.
0.5 ~
10.0 sec
2.0 sec
Programming