YASKAWA TM.iQp.10 Technical Manual Supplement
65
H5-03
0427
Communication Parity
Selection
Serial Com Sel
Selects the communication parity for Terminals R+, R-, S+ and S-.
0: No Parity
1: Even Parity
2: Odd Parity
Note: Drive power must be cycled before the changes will take effect.
<0034>
0 ~ 2
0
Programming
H5-04
0428
Stopping Method after
Communication Error
Serial Flt Sel
Selects the stopping method when a communication error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0 ~ 3
3
Programming
H5-05
0429
Communication Error
Detection Selection
Serial Flt Dtct
Enables or disables the communications timeout detection function.
0: Disabled - A communications loss will NOT cause a communications
fault.
1: Enabled - If communications are lost for more than the time specified in
parameter H5-09, a communications fault will occur.
0 ~ 1
1
Programming
H5-06
042A
Drive Transmit Wait Time
Transmit WaitTim
Sets the time from when the drive receives data to when the drive sends
data.
5 ~ 65 ms
5 ms
Programming
H5-07
042B
RTS Control Selection
RTS Control Sel
Enables or disables “request to send” (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)
0 ~ 1
1
Programming
H5-08
042C
Communication Protocol
Selection
Com Protocol Sel
0: MEMOBUS/Modbus
1: N2 (Metasys)
2: FLN (APOGEE)
0 ~ 2
0
Programming
H5-09
0435
Communication Error
Detection Time
CE Detect Time
Determines how long communications must be lost before a fault is
annunciated. Works in conjunction with parameters H5-05 and H5-04.
0.0 ~
10.0 sec
2.0 sec
Programming
Motor Overload
L1-01
0480
Motor Overload Protection
Selection
MOL Flt Sel
Enables or disables the motor thermal overload protection.
0: Disabled
1: Std Fan Cooled (Enabled)
2: Std Blower Cooled
3: Vector Motor
0 ~ 1
1
Programming
L1-02
0481
Motor Overload Protection
Time
MOL Time Const
Determines how much time will elapse prior to a motor overload fault
(OL1), when motor amps exceed the value set in parameter E2-01 by
10 %. Actual (OL1) trip time will vary depending on severity of overload.
0.1 ~
20.0 min
8.0 min
Programming
L1-03
0482
Motor Overheat Alarm
Operation Selection
Mtr OH Alarm Sel
Operation selection when the motor temperature analog input
(H3-09 = E) exceeds the OH3 alarm level (1.17 V)
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0 ~ 3
3
Programming
L1-04
0483
Motor Overheat Fault
Operation Selection
Mtr OH Fault Sel
Stopping method when the motor temperature analog input
(H3-09 = E) exceeds the OH4 level (2.34 V).
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
0 ~ 2
1
Programming
L1-05
0484
Motor Temperature Input
Filter Time
Mtr Temp Filter
Delay Time applied to motor temperature analog input (H3-09 = E) for
filtering purposes.
0.00 ~
10.00 sec
0.20 sec
Programming
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location