n005 : Stopping Method
Factory setting:
0
Range: 0 to 1
Selects the stopping method suitable for the application.
Setting
Description
0
Deceleration (ramp) to stop
1
Coast to stop
A.
Data
0 : Deceleration to Stop
Upon removal of the FWD (REV) Run
command, the motor decelerates at the
deceleration rate determined by the time
set in Decel Time 1 (
n020 ), and DC
injection braking is applied immediately
before stop. If the decel time is too short
or the load inertia is too large, an over-
voltage (OV) fault may occur on a stop
command — the decel time must be
increased.
B.
Data
1 : Coast to Stop
Upon removal of the FWD (REV) Run command, the motor coasts to rest.
5.24 STOPPING METHOD
Output Frequency
Run Command
ON
OFF
Decel Time 1
(
n020 )
Min. Output Frequency
(Frequency at DC Injection
Braking Start) (
n016 )
DC Injection Braking
Time at Stop (
n090 )
(Factory setting: 0.5 s)
Output Frequency
Run Command
ON
OFF
Drive output is shut OFF
when stop command is input