Example 6: Remote Sequence (2-Wire) & Remote Reference
(0 – 10 VDC) and three digital preset speeds
OPERATION:
• Close (K1) to Run Forward.
• Close (K2) to Run Reverse.
• If both (K1) & (K2) are closed, the drive stops and displays the error message: “EF.”
• Frequency reference is determined by the status of the switches (SW1) and (SW2).
• If the drive is put in the “Local” mode using the LO/RE quick start LED, the drive will behave the same as
illustrated in Example 1.
Table 7: Programming Required For Remote 2-wire Sequence & Multiple References
FS
FR
FC
DATA
ENTER
DSPL
RUN
MIN
MAX
REV
MULT
STEP 1
MULT STEP 2
0 - 10V
FREQ. REF
ANALOG
COMMON
FWD
Forward Run
Reverse Run
(K1)
S1
S2
S3
S4
S5
S6
S7
SC
STOP
RESET
FREF
FOUT
IOUT
MNTR
PRGM
LO/RE
F/R
Shield (Drain Wire)
To Terminal
Shield
(Drain Wire)
External
0 - 10 VDC
Source
Control Wiring Schematic
0. 0 0
(K2)
(+)
(–)
(SW1)
(SW2)
(SW1) Status
(SW2) Status
Reference Source
Open
Open
Analog value on terminal FR
Closed
Open
Digital value stored in parameter n025
Open
Closed
Digital value stored in parameter n026
Closed
Closed
Digital value stored in parameter n027
Parameter
Display
Description
n001
10
n001
4
n025
User Set
n026
User Set
n027
User Set
n036
Set Motor FLA
The drive will perform a 2-wire reset.
Setting this value will reset all parameters to their original factory
settings (all previous adjustments will be lost).
When the drive
completes the reset, this parameter returns to a value of 1.
CAUTION
After doing the reset above, the password parameter returned to a
1. Change it to a 4 to get access to all parameters in the drive.
Sets the frequency reference when switch (SW1) is closed and
switch (SW2) is open.
Sets the frequency reference when switch (SW1) is open and switch
(SW2) is closed.
Sets the frequency reference when switches (SW1) and (SW2) are
closed.
Enter the motor’s full load amps as shown on motor nameplate.