Yaskawa V7 Drives User Manual
Page 28

1-10
DATA
FUNCTION
DESCRIPTION*
S1
Multi-Function-Input 1
Factory setting is "
Forward Run/Stop " (1).
(Forward run when closed, stop when open)
S2
Multi-Function-Input 2
Factory setting is "
Reverse Run/Stop " (1).
(Reverse Run when closed, stop when open)
S3
Multi-Function-Input 3
Factory setting is "
External Fault (NO contact)
input " (1)
S4
Multi-Function-Input 4
Factory setting is "
Fault Reset " (1)
S5
Multi-Function-Input 5
Factory setting is "
Multi-step Speed
Reference 1 " (1)
S6
Multi-Function-Input 6
Factory setting is "
Multi-step Speed
Reference 2 " (1)
S7
Multi-Function-Input 7
Factory setting is "
Jog Reference" (1)
SC
Sequence common for terminals S1-S7.
Common terminal for sequence inputs
FS
Frequency reference power supply
+12 VDC
FR
Frequency reference input
0 to +10V/100% (20K ohms) or 4-20 mA (250
Ω)
RP
Frequency reference –Pulse Train input
30 KHz maximum pulse input
FC
Frequency reference input common
0 V
MA
Multi-function contact output – NO contact
Factory
Contact capacity:
MB
Multi-function contact output – NC contact
Setting
250 Vac at 1A or below
MC
Multi-function contact output – Common
is " Fault "
30 Vdc at 1A or below
AM
Multi-function analog monitor (+) Factory setting is
"
Output frequency "
0-10V = 0-100%
Monitor output: 0 to +10V; 2 mA maximum.
AC
Analog monitor common
0 V
P1
Multi-Function Open
Factory setting is
Collector Output 1
"
Drive Running "
Photocoupler output:
P2
Multi-Function Open
Factory setting is
48 VDC; 50 mA or less.
Collector Output 2
"
Speed Agree "
PC
Multi-Function Open
0 V
Collector Output common
R+
Receive input (+)
MODBUS
R–
Receive input (–)
communication
RS-485/422 MODBUS protocol,
S+
Send output (+)
RS-485 or RS-422.
19.2 kps max.
S–
Send output (–)
Table 1-3. Terminal Functions and Signals of Control Circuit
NOTES:
1.
These inputs have factory settings based on 2-wire reset. For 3-wire reset definitions, see Figure 1-6.
Continued
1.4 ELECTRICAL INSTALLATION