6-7
Fault Display
Digital
RUN (Green)
Drive
Explanation
Causes and
Operator
ALARM (Red)
Status
Corrective Actions
CPF-05
Cycle power.
A/D converter fault is
If the fault remains,
detected.
replace the drive.
CPF-06
Remove power to the
Option card connecting fault
drive.
Check the connection
of the digital operator.
CPF-07
Cycle power after checking
Operator control circuit
the digital operator is
(EEPROM or A/D
securely mounted.
converter) fault
If the fault remains,
replace the digital operator
or drive.
OPR (Operator
Cycle power.
connecting fault)
If the fault remains,
replace the drive.
CE (MODBUS
Check the communication
communications fault)
devices or communication
signals.
PF (Input Phase Loss)
Check input voltage.
Drive input power supply
Tighten terminal screws.
has an open phase or has
Check input voltage.
a large imbalance of voltage.
LF (Output Open Phase)
Check the wiring to the
An open phase occurred
motor.
at the Drive output.
Check motor for phase to
ground short.
Check motor impedance.
RH (Dynamic Braking
Resistor)
Table 6-2. Fault Displays and Corrective Actions - Continued
Protective
Operation.
Output is
shut OFF
and motor
coasts to a
stop.