A1-5, Table a1-1. drive parameters - continued – Yaskawa V7 Drives User Manual
Page 125

A1-5
PARA-
SETTING RANGE
SETTING
FACTORY
USER
PARA.
METER
NAME
(AND UNITS)
INCREMENT
SETTING
SETTING
REF.
0:
Detection Disabled
1:
Detect only at set frequency;
operation continues
2:
Detect only at set frequency;
n096
Overtorque Detection (OL3)
coast to stop
1
0
3:
Detect during all frequency conditions;
operation continues
4:
Detect during all frequency conditions;
coast to stop
5.20
Overtorque Detection
0:
Detected by output torque
1
0
n097
Selection (OL3)
1:
Detected by output current
n098
Overtorque Detection
Level (OL3)
30 to 200
1 (%)
160
n099
Overtorque Detection
Delay Time (OL3)
0.1 to 10.0
0.1 (sec)
0.1
n100
Up/Down Hold
0:
Disabled
Memory
1:
Enabled
1
0
5.10
n101
Speed Search
Deceleration Time
0.0 to 10.0
0.1 (sec)
2
5.18
n102
Speed Search Operation
Level
0 to 200%
1 (%)
150
5.18
n103
Torque Compensation Gain
0.0 to 2.5
0.1
1.0
(Note 4)
n104
Torque Compensation
5.26
Time Constant
0.0 to 25.5
0.1 (sec)
(Note 2)
n105
Torque Compensation
0.1 (W) or
Iron Loss
0.0 to 6550
1 (W)
(Note 1)
n106
Motor Rated Slip (Note 4)
0.0 to 20.0
0.1 (Hz)
(Note 1)
2.2, 5.22
n107
Motor Line-to-line
0.001 (ohm)
Resistance
0.000 to 65.50
(Note 1)
n108
Motor Leakage
0.01 (mH)
Inductance (Note 1)
0.00 to 655.0
or 0.1 (mH)
(Note 1)
n109
Torque Compensation
1 (%)
Limit
0 to 250
150
5.26
n110
Motor No-load Current
0 to 99
1 (%)
(Note 1)
2.2
n111
Slip Compensation Gain (Note 4)
0.0 to 2.5
0.1
(Note 2)
n112
Slip Compensation Primary
0.0 to 25.5
0.1 (sec)
(Note 2)
5.22
Delay Time
n113
Slip Compensation Selection
0:
Disabled
1
0
During Regeneration
1:
Enabled
0:
Disabled
n115
Stall Prevention Above Base
(level is based on setting of n094)
Speed During Run
1:
Enabled
1
0
(level at Fmax is n094 x 0.4)
0:
Follows acc/dec #1 (n019, n020)
5.23
or acc/dec #2 (n021, n022)
n116
Stall Prevention During Run,
Note: Multi-Function input selectable
1
0
Accel/Decel Time Select
1:
Follows acc/dec #2 (n021, n022)
always
0:
Undertorque detection disabled
1:
Detected during constant speed running.
Operation continues after detection
n117
Undertorque Detection
2:
Detected during constant speed running.
1
0
Select (UL3)
Operation stops during detection
3:
Detected during all frequency conditions.
Operation continues
4:
Detected during all frequency conditions.
coast to stop
5.34
0 to 200%
n118
Undertorque Detection
Inverter rated current = 100%; if n097 = 0
1(%)
0
Level (UL3)
(detection by torque); motor rated torque
becomes 100%
n119
Undertorque Detection
0.1 (sec)
Time (UL3)
0.1 to 10.0
0.1
n120
Frequency Reference 9 (Note 4)
0.00
n121
Frequency Reference 10 (Note 4)
0.01 (Hz)
0.00
n122
Frequency Reference 11 (Note 4)
(< 100 Hz)
0.00
n123
Frequency Reference 12 (Note 4)
0.00 to 400.00
or
0.00
5.11
n124
Frequency Reference 13 (Note 4)
0.1 (Hz)
0.00
n125
Frequency Reference 14 (Note 4)
(>= 100 Hz)
0.00
n126
Frequency Reference 15 (Note 4)
0.00
n127
Frequency Reference 16 (Note 4)
0.00
Table A1-1. Drive Parameters - Continued