Example 3: Remote Sequence (3-Wire) & Local Reference (Digital
Operator)
This configuration is best when a person rather than an external controller (PLC, relay, etc.) controls the drive.
OPERATION:
• The frequency reference comes from the digital operator pot.
• Close pushbutton (PB1) momentarily while pushbutton (PB2) is closed, and the drive will run at the
frequency setting in U1-01. Pushbutton (PB1) does
NOT need to be maintained.
• Open pushbutton (PB2) at any time and the drive will stop.
• If switch (SW1) is open, the drive will run in the forward direction. If switch (SW1) is closed, the drive will
run in the reverse direction. Switch (SW1) can be operated with the drive running at any speed.
• If the drive is put in the “Local” mode using the LO/RE quick start LED, the drive will behave the same as
illustrated in Example 1.
Table 4: Programming Required For Remote 3-wire Sequence & Local Reference
FS
FR
FC
DATA
ENTER
DSPL
RUN
MIN
MAX
STOP
FOR/REV
START
Start
Stop
Forward
(SW1)
(PB2)
(PB1)
Reverse
S1
S2
S3
S4
S5
S6
S7
SC
STOP
RESET
FREF
FOUT
IOUT
MNTR
PRGM
LO/RE
F/R
Shield (Drain Wire)
To Terminal
Control Wiring Schematic
0. 0 0
Parameter
Display
Description
n001
11
n001
4
n004
0
n036
Set Motor FLA
The drive will perform a 3-wire reset.
Setting this value will reset all parameters to their original factory
settings (all previous adjustments will be lost).
When the drive
completes the reset, this parameter returns to a value of 1.
CAUTION
After doing the reset above, the password parameter returned to a
1. Change it to a 4 to get access to all parameters in the drive.
This parameter sets the reference (motor speed) to come from the
digital operator potentiometer (local).
Enter the motor’s full load amps (as shown on the motor
nameplate).