Table 5-3. multi-function output terminals – Yaskawa V7 Drives User Manual
Page 81

5-29
Set
Description
Value
Condition
Signal Level
0
Fault
Closed = Drive fault has occurred (except CPF00, CPF01)
1
During operation
Closed = Drive is operating
2
Speed at set frequency
Closed = Frequency Reference = output frequency
See paragraph 5.19A
3
Zero Speed
Closed = Drive is at zero Hz.
4
Frequency detection - low
Closed = Output frequency
≤ n095.
See paragraph 5.19B
5
Frequency detection - high
Closed = Output frequency
≥ n095.
See paragraph 5.19C
6
Overtorque detection
Closed = Overtorque detected
(N.O. contact)
See paragraph 5.20
7
Overtorque detection
Open = Overtorque detected
(N.C. contact)
See paragraph 5.20
8
Under torque detection (NO)
Closed if under torque is detected
9
Under torque detection (NC)
Open if under torque is detected
10
Alarm (minor fault)
Closed = Alarm condition is present
11
During coast to stop
Closed = Drive output base block is active; motor is coasting
12
Local/Remote
Open = Frequency and Run Command by ext. input;
Closed = Frequency and Run Command by Digital Operator
13
Operation ready
Closed = Drive is ready for operation (not faulted)
14
Auto-restart
Closed = During auto-restart operation
15
During Undervoltage
Closed = Drive has an undervoltage fault or warning.
16
During Reverse run
Closed = Drive operation in reverse
17
During Speed Search
Closed = Drive performing a speed search
18
Serial communication
Closed = Command from serial communication
20
Frequency reference is missing
Closed if frequency reference is missing
21
Inverter overheating pre-alarm OH3
Closed if drive overheat pre-alarm is input at a Multi-function
Input. Digital operator display is “OH3” (blinking)
Table 5-3. Multi-function Output Terminals
5.19 MULTI-FUNCTION OUTPUT TERMINALS (Term, MA, MB & MC; P1, P2 & PC)