11 troubleshooting – Yaskawa SI-EN3/V EtherNet/IP for V1000 Drive User Manual
Page 47

11 Troubleshooting
YASKAWA ELECTRIC TOBP C730600 60A V1000 Option EtherNet/IP Installation Manual
47
■
Explicit Message Communications Errors
When there is a problem with a request message sent from the master in explicit
communications, the drive will return one of the following error codes.
Note: Refer to the MEMOBUS/Modbus Data Table in the Technical Manual for a list of monitor data
using the MEMOBUS/Modbus message area.
Error
Code
(hex)
Description
Cause
Possible Solution
08
Service not supported
The service code is incorrect.
Correct the service code.
09
Invalid attribute value
The attribute is incorrect.
Correct the attribute.
0C
Object state conflict
Attempted to change an drive constant
that cannot be changed while the drive
is running.
Stop the drive.
0E
Attribute not settable
Attempted to change a read-only
attribute.
Correct the service code or
attribute setting.
13
Not enough data
The data size is incorrect.
Correct the data size.
14
Attribute not supported
Attempted to execute a service not
defined for the attribute.
Correct the service code or
attribute setting.
15
Too much data
The data size is incorrect.
Correct the data size.
16
Object does not exist
An unsupported object was specified.
Correct the class or instance
setting.
1F
Vendor-specific error
Attempted to change a drive constant
that cannot be changed while the drive
is running.
Attempted to change a drive constant
to a value outside the setting range.
Stop the drive.
Specify a value within the
setting range.
20
Invalid parameter
Attempted to change to a data value
outside the setting range.
Specify a data value within the
setting range.
EtherNet_IM_E_conditional.fm 47 ページ 2012年3月16日 金曜日 午後6時5分