Extended speed control output - 21 (0x15), 8 output assemblies (drive consumes) – Yaskawa SI-EN3/V EtherNet/IP for V1000 Drive User Manual

Page 36

background image

8 Output Assemblies (Drive Consumes)

36

YASKAWA ELECTRIC TOBP C730600 60A V1000 Option EtherNet/IP Installation Manual

Extended Speed Control Output - 21 (0x15)

Output

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

21

0

NetRef

NetCtrl

Fault

Reset

Run
Rev

Run

Fwd

1

2

Speed Reference (Low Byte)

3

Speed Reference (High Byte)

Name

Description

Run Fwd

Forward Run Command
0: Stop
1: Forward Run

Run Rev

Reverse Run Command
0: Stop
1: Reverse Run

Fault Reset

Fault Reset
(0 to 1 transition: Fault Reset)

NetCtrl

Run command from Network
0: Depends on b1-02
1: Enables the run command from network

NetRef

Speed reference from Network
0: Depends on b1-01
1: Enables the speed reference from network

Speed Reference

Speed Command
Sets drive speed reference.
Speed reference data:
Frequency reference/2

SS

(SS: Speed scale)

Setting range: 0 to 0xFFFF
For example, when setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/2

2

= 1024 = 0x0400

Unit depends on o1-03.