V1000 – Yaskawa SI-EN3/V EtherNet/IP for V1000 Drive User Manual
Page 27

5 Installation Procedure
YASKAWA ELECTRIC TOBP C730600 60A V1000 Option EtherNet/IP Installation Manual
27
13.
Connect the ground wire at the option ground terminal. Tighten the screw to 0.5 to
0.6 Nxm or (4.4 to 5.3 in lbs) using an M3 Phillips screwdriver.
Figure 17
Figure 17 Connect the Ground Wire to the Option
14.
To connect the option to a network, firmly connect RJ45 8-pin Shielded Twisted Pair
Cat 5e cable(s) into the modular connector port.
Note: Do not connect or disconnect the communication cable while the drive is powered up or while
the drive is in operation. Failure to comply may cause a static discharge, which will cause the
option card to stop working properly. Cycle power on the drive and option card to reestablish
functionality.
Figure 18
Figure 18 Communication Cable Port
Option ground terminal
V1000
V1000