6 Related Drive Parameters
YASKAWA ELECTRIC TOBP C730600 60A V1000 Option EtherNet/IP Installation Manual
33
Table 9 Option Monitors
F7-33 to
F7-42
(405 to 40E)
Dynamic Input Assembly
Parameters
Parameters used in Input Assembly 166. Each
parameter contains a MEMOBUS/Modbus
address. The value sent for Input Assembly 166
will be read from this corresponding MEMOBUS/
Modbus address. A MEMOBUS/Modbus address
value of 0 means that the value sent for Input
Assembly 166 is not defined by the user, therefore
the option default register value will be returned.
Refer to Input Assemblies (Drive Produces) on
page 37
for definitions of the default MEMOBUS/
Modbus registers.
Default: 0
<1> To start and stop the drive with the EtherNet/IP master device using serial communications, set b1-02 to 3 or set
the “Net Control” bit in the assemblies or Control Supervisor Object. To control the drive frequency reference of
the drive via the master device, set b1-01 to 3 or set the Net Reference bit in the assemblies or AC/DC Object.
<2> If F6-01 is set to 3, the drive will continue to operate when a fault is detected. Take safety measures, such as
installing an emergency stop switch.
<3> Cycle power for setting changes to take effect.
<4> If F7-13 is set to 0, then all IP Addresses (F7-01 to F7-04) must be unique.
<5> Set F7-01 to F7-12 when F7-13 is set to 0.
<6> Default setting differs by drive software version.
1012 to 1015: 0
≥ 1016: 1
<7> Set F7-15 when F7-14 is set to 0 or 2.
<8> The setting values differ by drive software version.
1012 to 1015
Default: 0
Range: 0, 10, 100
≥ 1016
Default: 10
Range: 10, 100
No.
Name
Description
Value Range
U6-80 to U6-83
Online IP Address
IP Address currently available; U6-80 is the most
significant octet
0 to 255
U6-84 to U6-87
Online Subnet
Subnet currently available; U6-84 is the most
significant octet
0 to 255
U6-88 to U6-91
Online Gateway
Gateway currently available; U6-88 is the most
significant octet
0 to 255
U6-92
Online Speed
Link Speed
10: 10 Mbps
100: 100 Mbps
U6-93
Online Duplex
Duplex Setting
0: Half, 1: Full
U6-98
First Fault
First Option Fault
–
U6-99
Current Fault
Current Option Fault
–
No.
(Addr.
Hex)
Name
Description
Values