10 apogee fln p1 communications – Yaskawa APOGEE FLN P1 User Manual
Page 41
Point
No.
Point
Type
Point Name
Factory
Default
(SI Units)
Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
Parameter
54
LAO
POWER LOSS RT
0.1
s
0.1
0
-
-
L2-02
55
LAO
RUN OP MODE
1
-
1
0
-
-
b1-02
56
LAO
REF OP MODE
1
-
1
0
-
-
b1-01
57
LAO
OPER DISP MD
0
-
1
0
-
-
o1-03
58
LDI
MF IN 1 MON
OFF
-
1
0
ON
OFF
U1-10
(Bit 2)
59
LDI
MF IN 2 MON
OFF
-
1
0
ON
OFF
U1-10
(Bit 3)
60
LAO
INPUT REF 1
0
Hz
0.01
0
-
-
-
61
LAO
INPUT REF 2
0
Hz
0.01
0
-
-
d1-02
62
LAI
PID FEEDBACK
0
%
0.01
0
-
-
U5-01
63
LAO
PID P GAIN
2
-
0.01
0
-
-
b5-02
64
LAO
PID I TIM
0.5
s
0.1
0
-
-
b5-03
65
LDO
PID MODE SEL
DISABLE
-
1
0
ENABLE
DISABLE
b5-01
66
LAI
LST FLT CODE
0
-
1
0
-
-
U2-02
67
LAI
FREF.FLT
0
Hz
0.01
0
-
-
U2-03
68
LAI
OUT FREQ FLT
0
Hz
0.01
0
-
-
U2-04
69
LAI
OUT CUR.FLT
0
A
0.01
0
-
-
U2-05
70
LAO
RD PARAM NUM
1
-
1
0
-
-
-
71
LAI
RD PARAM DAT
0
-
1
0
-
-
-
72
LAO
WR PARAM NUM
1
-
1
0
-
-
-
73
LAO
WR PARAM DAT
0
-
1
0
-
-
-
74
LDI
MF IN 3 MON
OFF
-
1
0
ON
OFF
U1-10
(Bit 4)
75
LAI
OUT VOLT.FLT
0
V
0.1
0
-
-
U2-07
76
LAI
DC BUS.FLT
0
V
1
0
-
-
U2-08
77
LAI
OUT PWR.FLT
0
kW
0.1
0
-
-
U2-09
78
LDI
MF IN 4 MON
OFF
-
1
0
ON
OFF
U1-10
(Bit 5)
79
LAI
PID DEVIATE
0
%
0.01
0
-
-
U5-02
80
LAO
PID I LIMIT
100
%
0.1
0
-
-
b5-04
81
LAO
PID UP LIMIT
100
%
0.1
0
-
-
b5-06
82
LAO
PID OFFS ADJ
100
%
0.1
-100
-
-
b5-07
83
LAO
PID PRI DYTM
0
s
0.1
0
-
-
b5-08
84
LAO
PID FB RMDS
0
-
1
0
-
-
b5-12
10 APOGEE FLN P1 Communications
YASKAWA TOEP YAICOM 13 Metasys N2 & Apogee FLN P1 SI-J3 Installation & Technical Manual
41